2008-09-26 13:50:17 | 2004 FBC W/2007 REVISIONS |
| NSFD |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. FS713 |
| |
| 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY 'C' |
| PER FBC R301.2.1.4. THE BUILDING IS DIRECTLY ADJACENT |
| TO OPEN AREAS OF EXPOSURE C TYPE TERRAIN FOR A DISTANCE |
| OF MORE THAN 600 FEET. PLEASE REVISE PLANS. SEE SHEETS |
| T1, A4 AND A5. |
| |
| 3) SHOW COMPLIANCE WITH FBC R302.1 EXTERIOR WALLS. |
| EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| AN ADJACENT PROJECTION OR WALL.PROJECTIONS EXTENDING |
| INTO THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL |
| HAVE NOT LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION |
| ON THE UNDERSIDE. THE ABOVE PROVISIONS SHALL NOT APPLY |
| TO WALLS WHICH ARE PERPENDICULAR TO A LINE EXTENDING |
| FROM THE POINT FROM WHICH THE SEPARATION DISTANCE HAS |
| BEEN MEASURED RUNNING AND PARALLEL TO THE PROPERTY |
| LINE. THE DISTANCE FROM SOME OF THE STRUCTURE'S WALLS |
| TO THE PROPERTY LINES ARE LESS THAN SIX FEET. SUBMIT 2 |
| SURVEYS OR SITE PLANS THAT SPECIFY THE DISTANCES TO |
| STRUCTURES ON ADJACENT PROPERTIES AT THESE LOCATIONS. |
| |
| 4) SHOW COMPLIANCE WITH R302.2 OPENINGS. |
| OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF |
| A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM |
| AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET |
| (1828 MM). THIS DISTANCE SHALL BE MEASURED |
| PERPENDICULAR TO THE LINE USED TO DETERMINE THE |
| SEPARATION DISTANCE. |
| |
| 5) PLEASE REVISE THE WINDOW AND DOOR OPENING PRESSURES |
| LISTED ON SHEETS A4 AND A5 TO EXPOSURE C. FBC R 301.2.1 |
| |
| 6) THE PLANS SPECIFY CONCRETE ROOF TILE ON SHEET A4 AND |
| THE SECTION ON A6 SPECIFIES CLAY ROOF TILE. PLEASE |
| CORRECT. |
| |
| 7) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE |
| ROOF COVERING THAT WILL BE INSTALLED. FAC RULE 9B-72 |
| |
| 8) SHEET A2 OF THE PLANS SPECIFIES 2" X 6" X 1/8" MULLS |
| AT THE LIVING ROOM WINDOWS. THE PRODUCT APPROVALS THAT |
| WERE SUBMITTED ARE FOR 2" X 6" X .250" (1/4") MULLIONS. |
| PLEASE REVISE PLANS. |
| |
| 9) SHEET A2 OF THE PLANS SPECIFIES 1" X 4" X 1/8" MULLS |
| AT THE BREAKFAST ROOM WINDOWS. THE PRODUCT APPROVALS |
| THAT WERE SUBMITTED ARE FOR 1" X 4" X .375" (3/8") |
| MULLIONS. PLEASE REVISE PLANS. |
| |
| 10) THE PRODUCT APPROVALS FOR THE 1X HEAVY WALL |
| MULLIONS ARE MISSING THE UPPER PART OF THE INSTALLATION |
| DRAWINGS AND TABLES. PLEASE SUBMIT COMPLETE DRAWINGS. |
| FAC RULE 9B-72. |
| |
| 11) PRODUCT APPROVALS FOR A MASONITE INTERNATIONAL DOOR |
| FL# 4940 WERE SUBMITTED. PLEASE SPECIFY WHERE THIS DOOR |
| WILL BE LOCATED. FBC R301.2.1 |
| |
| 12) THE PRODUCT APPROVAL NOA # 05-1129.11 FOR THE PGT |
| C-740 CASEMENT WINDOWS IS EXPIRED. PLEASE SUBMIT THE |
| NEW ONE, NOA# 08-0117.11. FAC RULE 9B-72 |
| |
| 13) THE PRODUCT APPROVAL NOA # 06-0807.07 FOR THE PGT |
| FD101 OUTSWING FRENCH DOOR IS EXPIRED. PLEASE SUBMIT |
| THE NEW ONE, NOA# 07-0629.10. FAC RULE 9B-72 |
| |
| NOTE: IN ORDER TO AVOID ANY DELAYS IN GETTING THE |
| PERMIT ISSUED, PLEASE REVIEW DESIGN PRESSURES OF ALL |
| PRODUCTS REQUIRING PRODUCT APPROVAL TO MAKE SURE THEY |
| WILL BE ADEQUATE FOR THE HIGHER COMPONENT AND CLADDING |
| PRESSURES OF EXPOSURE CATEGORY C. |
| NOTE: PLEASE RESUBMIT THE SHEETS FROM THE OLD PLANS |
| WITH THE IMPACT FEE STAMPS ON THEM. |
| |