| ** TEMP FAILED REVIEW** |
| |
| |
| ** THERE ARE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE |
| STILL IN NEED OF BEING ADDRESSED. |
| ** SPOKE TO DEVRON FROM RELIABLE DESIGN. |
| |
| 1) NOTE: PLEASE SEE 13-415.2.ABC.1 FOR PERFORMANCE |
| PROCEDURES. MAY NOT USE TWO METHODS TO DERIVE AT TOTAL. |
| PLANS SHOWS SPACE BY SPACE METHOD (TABLE B) AND WHOLE |
| SPACE METHOD FROM TABLE C. MAY NOT USE BOTH. |
| |
| A NEW CORRECTED SHEET WILL BE NEEDED. |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |