Plan Review Notes
Plan Review Notes For Permit 08090268
Permit Number 08090268
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-24 09:36:23** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE FBC 13-415.2,13-415.2.ABC.1.1,.1.2
 AND TABLE 13-415.2.B.1, 13-415.2.C.1. THE FORM *C* AS
 SUBMITTED EXCEEDS THE LIGHTING LEVELS PERMITTED IN THE
 FBC 13-415.2.C.1.
  
  
  
  