2009-10-28 16:26:03BUILDING PLAN REVIEW
 PERMIT: 08090247
 ADD: 501 N ROSEMARY AVE
 CONT: NUJAK DEVELOPMENT
 TEL: (863)686-1565
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
 OCT. 28/2009
  
 LETTER OF OCT 21/2009 IN REGARDS TO FOAM PLASTIC WALL
 INSULATION, PLEASE REFER TO SECTION :
 2004 FBC- BUILDING 2603.5.2 THERMAL BARRIER.
 ANY FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 BUILDING INTERIOR BY A THERMAL BARRIER MEETING THE
 PROVISIONS OF SECTION 2603.4, UNLESS SPECIAL APPROVAL
 IS OBTAINED ON THE BASIS OF SECTION 2603.8.
  
  
 PLEASE REVIEW THE MECHANICAL PLANS THE AREA ABOVE THE
 CEILING IS CONSIDERED A PLENUM:
 2004 FBC MECHANICAL 602.2.1 MATERIALS EXPOSED WITHIN
 PLENUMS.
 EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH
 602.2.1.5, MATERIALS EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2004 MECHANICAL 602.2.1.5 FOAM PLASTIC INSULATION.
 FOAM PLASTIC INSULATION USED AS WALL OR CEILING FINISH
 IN PLENUMS SHALL EXHIBIT A FLAME SPREAD INDEX OF 75 OR
 LESS AND A SMOKE-DEVELOPED INDEX OF 450 OR LESS WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 AND SHALL ALSO
 COMPLY WITH SECTION 602.2.1.5.1, 602.2.1.5.2 OR
 602.2.1.5.3.
 602.2.1.5.1 SEPARATION REQUIRED.
 THE FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 PLENUM BY A THERMAL BARRIER COMPLYING WITH SECTION
 2603.4 OF THE FLORIDA BUILDING CODE, BUILDING.
 602.2.1.5.2 APPROVAL.
 THE FOAM PLASTIC INSULATION SHALL BE APPROVED BASED ON
 TESTS CONDUCTED IN ACCORDANCE WITH SECTION 2603.8 OF
 THE FLORIDA BUILDING CODE, BUILDING .
 602.2.1.5.3 COVERING.
 THE FOAM PLASTIC INSULATION SHALL BE COVERED BY
 CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS
 OF NOT LESS THAN 0.0160 INCH (0.4 MM).
  
 2004 MECANICAL 603.8 CAVITIES OF THE BUILDING
 STRUCTURE.
 CAVITIES IN FRAMED SPACES, SUCH AS DROPPED SOFFITS AND
 WALLS, SHALL NOT BE USED TO DELIVER AIR FROM OR RETURN
 AIR TO THE CONDITIONING SYSTEM UNLESS THEY CONTAIN AN
 AIR DUCT INSERT WHICH IS INSULATED IN ACCORDANCE WITH
 TABLE 13-410.1.ABC.2.2 OR TABLE 13-610.1.ABC.2.1 OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE, BUILDING AND
 CONSTRUCTED AND SEALED IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 603.1 APPROPRIATE FOR THE DUCT
 MATERIALS USED.
 EXCEPTION: RETURN AIR PLENUMS.
 CAVITIES DESIGNED FOR AIR TRANSPORT SUCH AS MECHANICAL
 CLOSETS, CHASES, AIR SHAFTS, ETC. SHALL BE LINED WITH
 AN AIR BARRIER AND SEALED IN ACCORDANCE WITH SECTION
 603.9 AND SHALL BE INSULATED IN ACCORDANCE WITH TABLE
 13-410.1.ABC.2.2 OR TABLE 13-610.1.ABC.2.1 OF CHAPTER
 13 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING CAVITIES WHICH WILL BE USED AS RETURN AIR
 PLENUMS SHALL BE LINED WITH A CONTINUOUS AIR BARRIER
 MADE OF DURABLE NON-POROUS MATERIALS. ALL PENETRATIONS
 OF THE AIR BARRIER SHALL BE SEALED WITH A SUITABLE
 LONG-LIFE MASTIC MATERIAL.
 EXCEPTION: SURFACES BETWEEN THE PLENUM AND CONDITIONED
 SPACES FROM WHICH THE RETURN/MIXED AIR IS DRAWN.
 BUILDING CAVITIES BENEATH A ROOF DECK THAT WILL BE USED
 AS RETURN AIR PLENUMS SHALL HAVE AN INSULATED ROOF WITH
 THE INSULATION HAVING AN R-VALUE OF AT LEAST R-19.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved