Plan Review Notes
Plan Review Notes For Permit 08090247
Permit Number 08090247
Review Stop ENG
Sequence Number 4
Notes
Date Text
2009-07-08 13:00:49APPROVED WITH PROVISOS:
 DEAN S. LAUDERMILK, PROJECT COORDINATOR, CONTACT NUMBER
 494-1083 (ENGINEERING) 805-6716 (CONSTRUCTION SERVICES)
 1. IF AN AIR RIGHTS EASEMENT HAS BEEN APPLIED FOR THIS
 COMMENT IS NO LONGER VALID. IF AN AIR RIGHTS EASEMENT
 HAS NOT BEEN APPLIED FOR THEN ONE NEEDS TO BE APPLIED
 FOR AND APPROVED PRIOR TO GETTING A CO. NO PERMANENT
 STRUCTURES ARE ALLOWED IN CITY ROW (BALCONY ABOVE
 ENTRANCE DOOR).
 2. DOORS ARE NOT ALLOWED TO OPEN OUT INTO A SIDEWALK
 AND OR ROW. THE ENTRANCE DOOR ON RODSEMARY TO THE
 RECEPTION AREA NEEDS TO BE RECESSED OR REDESIGNED TO
 OPEN IN.
 3. IRRIGATION PLAN NEEDS TO BE MODIFIED. THE
 ENGINEERING REVIEW INVOLVES THE SIZE OF METERS TO BE
 USED.
 A) IRRIGATION SYSTEM ZONES, GALLON PER MINUTE (GPM)
 FLOWS MUST BE SHOWN (PER SHEET IR-1 THE 4 ZONES ARE
 CALLED OUT). THE VALVE INFORMATION DETAIL ON IR-2
 SHOWS, THE ZONE NUMBER, GALLONS PER MINUTE OF EACH ZONE
 AND SIZE OF VALVE FOR EACH ZONE NEEDS TO BE CALLED OUT,
 THEY ARE NOT. THEN SEE NOTE IR-B.
 B) A 5/8" WATER METER IS CALLED OUT FOR IRRIGATION
 USAGE ON IR-1 IN THE NOTES SECTION. A 5/8" WATER METER
 WILL ONLY GIVE 10 GPM (SAFE OPERATING FLOW). IF ANY
 ZONE IS LARGER THAN THIS THE METER SIZE SHALL NEED TO
 BE INCREASED. A 3/4" WATER METER WILL GIVE 15 GPM AND A
 1" WATER METER WILL GIVE 25 GPM. IF ANY ZONE IS OVER 10
 GPM THEN REDESIGN THE IRRIGATION SYSTEM OR INCREASE THE
 METER SIZE ACCORDANTLY.
 4. IF THE STORMWATER PRE AND POST SQUARE FOOTAGE HAS
 BEEN GIVEN TO ENGINEERING THIS NOTE IS NO LONGER VALID.
 IF THE INFORMATION HAS NOT BE RECIEVED THEN FORWARD THE
 PRE AND POST PERVIOUS AND IMPERVIOUS SQ. FOOTAGE TO
 ENGINEERING. THIS WILL BE CHECKED AND CAN HOLD UP THE
 CO ON THE BUILDING.