2009-03-29 10:56:34** DENIED REVIEW **
 3RD REVIEW
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW, THE SYSTEM PER
 FBC 3006.2 IS NOT ON ELECTRICAL PLANS. THE RESPONSE
 LETTER MENTIONS TO SEE NOTE #1 IN LETTER HOWEVER THAT
 NOTE #1 WAS SPECIFIC TO CIRCUIT H-8 FROM PREVIOUS
 REVIEW.
 THIS HAS BEEN NOTED IN THE LAST THREE REVIEWS. WHERE IS
 THE DEDICATED CIRCUITING? WHERE THESE ON THE PANEL ARE
 SCHEDULES AS DEDICATED CIRCUITS?
 THE ONLY REVISION TO THIS NOW IS CIRCUIT H-38 WHICH IS
 NOT DEDICATED FOR THE FAN. IT CAN NOT BE ON WITH ANY
 OTHER DEVICES.
 THE SYSTEM NEEDS TO BE INDEPENDENT.
  
 ** A SEPARATE INFORMATIONAL; PLEASE TAKE A LOOK AT 2004
 ASME-17 FOR ELEVATOR CODE REQUIREMENTS. THERE ARE
 SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT.
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT
 COMPLETE WITH ALL ELECTRICAL ITEMS ON PLANS IN THE
 INPUT DATA REPORT. MANY EXAMPLES WERE GIVEN ON PREVIOUS
 REVIEWS HOWEVER THE IDR IS STILL MISSING ELECTRICAL
 ITEMS.
 AN EXAMPLE: THERE IS A 12KW ELECTRIC WATER HEATER ON
 PLANS YET THE IDR IS BLANK. ANOTHER WOULD BE THE HW
 PIPING WHICH GOES ALONG WITH THIS.
 THESE ARE MINIMUMS IN THE CODE.
 PLEASE CORRELATE.
 13-412.1.ABC.4, 13-412, 13-400.B.3 ETC
  
 *** KEEP IN MIND THERE MAY BE OTHER BUILDING COMPONENTS
 WHICH ARE NOT IN THE IDR WHICH MAY BE NOTED BY OTHER
 TRADES.
  
 3) NOTE: SERVICE HAS BEEN REVISED. NEED TO SHOW LOAD
 CALCULATIONS TO BE SHOWN FOR THE NEW 800AMP MAIN.
 PLEASE ALSO INCLUDE LOAD ON THE HOUSE METER. THE
 ELEVATOR IS SHOWN BEING TAPPED FROM THE 400AMP METER
 ALONG WITH THE HOUSE PANEL. THE ONLY LOAD SHOWN FOR THE
 HOUSE METER IS THE LOAD ON THE HOUSE PANEL.
 NEC220
  
 4) NOTE: PLEASE BE SURE WHEN SEALING THE PLANS ( SEE
 NEW SHEETS) THE SEAL IS CLEAR AND VISIBLE. THE NEW
 SHEETS IN SETS ARE VERY FAINT AND SOME CAN NOT BE SEEN
 EVEN USING LEAD RUB.
 FS 471.0221.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved