2009-03-29 10:56:34 | ** DENIED REVIEW ** |
| 3RD REVIEW |
| |
| 1) NOTE: AS NOTED ON PREVIOUS REVIEW, THE SYSTEM PER |
| FBC 3006.2 IS NOT ON ELECTRICAL PLANS. THE RESPONSE |
| LETTER MENTIONS TO SEE NOTE #1 IN LETTER HOWEVER THAT |
| NOTE #1 WAS SPECIFIC TO CIRCUIT H-8 FROM PREVIOUS |
| REVIEW. |
| THIS HAS BEEN NOTED IN THE LAST THREE REVIEWS. WHERE IS |
| THE DEDICATED CIRCUITING? WHERE THESE ON THE PANEL ARE |
| SCHEDULES AS DEDICATED CIRCUITS? |
| THE ONLY REVISION TO THIS NOW IS CIRCUIT H-38 WHICH IS |
| NOT DEDICATED FOR THE FAN. IT CAN NOT BE ON WITH ANY |
| OTHER DEVICES. |
| THE SYSTEM NEEDS TO BE INDEPENDENT. |
| |
| ** A SEPARATE INFORMATIONAL; PLEASE TAKE A LOOK AT 2004 |
| ASME-17 FOR ELEVATOR CODE REQUIREMENTS. THERE ARE |
| SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT. |
| |
| 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT |
| COMPLETE WITH ALL ELECTRICAL ITEMS ON PLANS IN THE |
| INPUT DATA REPORT. MANY EXAMPLES WERE GIVEN ON PREVIOUS |
| REVIEWS HOWEVER THE IDR IS STILL MISSING ELECTRICAL |
| ITEMS. |
| AN EXAMPLE: THERE IS A 12KW ELECTRIC WATER HEATER ON |
| PLANS YET THE IDR IS BLANK. ANOTHER WOULD BE THE HW |
| PIPING WHICH GOES ALONG WITH THIS. |
| THESE ARE MINIMUMS IN THE CODE. |
| PLEASE CORRELATE. |
| 13-412.1.ABC.4, 13-412, 13-400.B.3 ETC |
| |
| *** KEEP IN MIND THERE MAY BE OTHER BUILDING COMPONENTS |
| WHICH ARE NOT IN THE IDR WHICH MAY BE NOTED BY OTHER |
| TRADES. |
| |
| 3) NOTE: SERVICE HAS BEEN REVISED. NEED TO SHOW LOAD |
| CALCULATIONS TO BE SHOWN FOR THE NEW 800AMP MAIN. |
| PLEASE ALSO INCLUDE LOAD ON THE HOUSE METER. THE |
| ELEVATOR IS SHOWN BEING TAPPED FROM THE 400AMP METER |
| ALONG WITH THE HOUSE PANEL. THE ONLY LOAD SHOWN FOR THE |
| HOUSE METER IS THE LOAD ON THE HOUSE PANEL. |
| NEC220 |
| |
| 4) NOTE: PLEASE BE SURE WHEN SEALING THE PLANS ( SEE |
| NEW SHEETS) THE SEAL IS CLEAR AND VISIBLE. THE NEW |
| SHEETS IN SETS ARE VERY FAINT AND SOME CAN NOT BE SEEN |
| EVEN USING LEAD RUB. |
| FS 471.0221. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |