Date |
Text |
2009-02-09 09:50:04 | ** DENIED 2ND REVIEW ** |
| |
| ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF |
| ADDRESSING FROM THE PREVIOUS REVIEWS. |
| |
| |
| 1) NOTE: PLEASE SEE THE CIRCUITING IN THE ELEVATOR |
| MACHINE ROOM AND ELEVATOR ARE SHOWN NOW ON THE SAME |
| CIRCUIT FOR H-8. PANEL SCHEDULE STATES RECEPTS/LIGHTS |
| FOR ELEVATOR PIT HOWEVER BASED ON THE PLANS THESE ARE |
| BEING SHARD INTO OTHER AREAS WHICH IS NOT PERMITTED. |
| PLEASE SEE 680.22-680.24. DEDICATED CIRCUITS ARE |
| REQUIRED FOR EACH OF THE SPACES AS LISTED INCLUDING FOR |
| THE ELEVATOR CAR ITSELF. |
| PLEASE SEE THE NEXT COMMENT AS THIS IS AFFECT BY THE |
| SAME NOTE. |
| |
| 2) NOTE: PLEASE SEE FBC 3006.2 WITH THE REQUIRED |
| INDEPENDENT SYSTEM FOR THE ELEVATOR MACHINE ROOM. THIS |
| WOULD REQUIRE DEDICATED CIRCUITING AS NOTED ABOVE IN |
| COMMENT #1. ( NOTED PREVIOUS REVIEW ) |
| |
| 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH |
| RESPECT TO FBC CHAPTER 13. COMPLIANCE FOR MINIMUM HAS |
| NOT BEEN MET. |
| |
| A) THE SQUARE FOOTAGE ON PLANS AND CALCULATIONS |
| SUBMITTED DO NOT COORDINATE. |
| |
| B) THE PLANS CONTAINS A METHOD *B* TABLE CALCULATION |
| FOR SPACE BY SPACE. IT IS NOT PERMISSIBLE TO MIX |
| METHODS OF CALCULATIONS. PLEASE SEE 13-415.2.ABC.1 |
| |
| C) PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT |
| ALSO NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. THE |
| INPUT DATA REPORT WILL BE NOTED AS IDR ON THE REMAINDER |
| OF THIS COMMENT. |
| THERE ARE STILL LIGHTING FIXTURES ON PLANS WHICH ARE |
| NOT IN THE IDR OR FIXTURE WATTAGES WHICH DO NOT |
| COORDINATE. |
| |
| FOR EXAMPLE: PLEASE SEE THE COUNT ON THE EXTERIOR |
| LIGHTS, WATTAGES DO NOT COORDINATE. THE IDR ONLY |
| INDICATE 2-500WATT FIXTURES AND 8-46 WATT FIXTURES. |
| THERE ARE ACTUALLY MORE FIXTURES ON PLANS BY COUNT AND |
| WATTAGE. |
| |
| FOR EXAMPLE: INTERIOR LIGHT FIXTURES SHALL INCLUDE ALL |
| AREAS. BASED ON THE IDR, IT ONLY LIST TWO DIFFERENT |
| TYPE OF FIXTURES. BASED ON THE PLANS AND THE FIXTURE |
| LEGEND THIS IS NOT THE CASE. |
| |
| FOR EXAMPLE: FIXTURES NEED TO BE SPECIFIC. MOST |
| FIXTURES STATE *TBD* WHICH THE VA RATING CAN NOT BE |
| VERIFIED. PLEASE SELECT SPECIFIC FIXTURES. THESE MAY |
| ALWAYS BE REVISED AT A LATER DATE IF A PRODUCT CHANGES. |
| THE GOAL IS AT LEAST TO MEET THE MINIMUM CODES. |
| *D* FIXTURES ARE SHOWN ON PLANS HOWEVER HAVE DIFFERENT |
| SYMBOLS. WHEN LOOKING AT THE SYMBOL LEGEND YOU WILL SEE |
| EACH OF THESE ARE ACTUALLY DIFFERENT. ONE IS 58VA AND |
| THE OTHER 29 VA. |
| |
| |
| *** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT TO |
| HELP. THESE MAY NOT BE ALL ITEMS. IT IS IMPORTANT TO |
| FIGURE HOW CALCULATIONS WILL BE DONE FOR EACH SPACE OR |
| AS PART OF THE BUILDING. |
| PLEAS BE SURE TO GO OVER AND CALL WITH ANY COMMENTS OR |
| QUESTIONS FOR COORDINATION. |
| 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3. |
| |
| 4) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE CONTROLS |
| REQUIRED FOR CONFERENCE ROOM. ( NOTED ON PREVIOUS |
| REVIEW) |
| |
| 5) NOTE: BASED ON A COMPLETE REVISED ELECTRICAL RISER, |
| PLEASE SEE 230.70. THERE ARE UNPROTECTED CONDUCTORS |
| INSIDE THE BUILDING WHICH IS NOT PERMITTED. THE CODE |
| SECTION GIVEN DOES NOT GIVE AN AMOUNT PERMITTED. |
| THE OLD PALM BEACH COUNTY AND CITY OF WEST PALM BEACH |
| TECHNICAL AMENDMENTS PERMITTED UP TO 8FT, HOWEVER AS |
| THE OLDER CODE CHANGED THE TECHNICAL AMENDMENTS WENT |
| AWAY. SOME MUNICIPALITIES DO NOT PERMIT ANY UNPROTECTED |
| CONDUCTORS INSIDE THE BUILDING. |
| THE AMOUNT AS SHOWN ON PLANS IS OVER. PLEASE ADJUST |
| DESIGN. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
2009-02-06 17:00:40 | REVIEW TO CONTINUE. REVIEW WILL GO INTO A FAILED STATUS |
| ONCE COMPLETE. SOME NOTES FROM PREVIOUS REVIEW AND |
| MEETING STILL NEED TO BE ADDRESSED. |