Plan Review Notes
Plan Review Notes For Permit 08090247
Permit Number 08090247
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-09 09:50:04** DENIED 2ND REVIEW **
  
 ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF
 ADDRESSING FROM THE PREVIOUS REVIEWS.
  
  
 1) NOTE: PLEASE SEE THE CIRCUITING IN THE ELEVATOR
 MACHINE ROOM AND ELEVATOR ARE SHOWN NOW ON THE SAME
 CIRCUIT FOR H-8. PANEL SCHEDULE STATES RECEPTS/LIGHTS
 FOR ELEVATOR PIT HOWEVER BASED ON THE PLANS THESE ARE
 BEING SHARD INTO OTHER AREAS WHICH IS NOT PERMITTED.
 PLEASE SEE 680.22-680.24. DEDICATED CIRCUITS ARE
 REQUIRED FOR EACH OF THE SPACES AS LISTED INCLUDING FOR
 THE ELEVATOR CAR ITSELF.
 PLEASE SEE THE NEXT COMMENT AS THIS IS AFFECT BY THE
 SAME NOTE.
  
 2) NOTE: PLEASE SEE FBC 3006.2 WITH THE REQUIRED
 INDEPENDENT SYSTEM FOR THE ELEVATOR MACHINE ROOM. THIS
 WOULD REQUIRE DEDICATED CIRCUITING AS NOTED ABOVE IN
 COMMENT #1. ( NOTED PREVIOUS REVIEW )
  
 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO FBC CHAPTER 13. COMPLIANCE FOR MINIMUM HAS
 NOT BEEN MET.
  
 A) THE SQUARE FOOTAGE ON PLANS AND CALCULATIONS
 SUBMITTED DO NOT COORDINATE.
  
 B) THE PLANS CONTAINS A METHOD *B* TABLE CALCULATION
 FOR SPACE BY SPACE. IT IS NOT PERMISSIBLE TO MIX
 METHODS OF CALCULATIONS. PLEASE SEE 13-415.2.ABC.1
  
 C) PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT
 ALSO NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. THE
 INPUT DATA REPORT WILL BE NOTED AS IDR ON THE REMAINDER
 OF THIS COMMENT.
 THERE ARE STILL LIGHTING FIXTURES ON PLANS WHICH ARE
 NOT IN THE IDR OR FIXTURE WATTAGES WHICH DO NOT
 COORDINATE.
  
 FOR EXAMPLE: PLEASE SEE THE COUNT ON THE EXTERIOR
 LIGHTS, WATTAGES DO NOT COORDINATE. THE IDR ONLY
 INDICATE 2-500WATT FIXTURES AND 8-46 WATT FIXTURES.
 THERE ARE ACTUALLY MORE FIXTURES ON PLANS BY COUNT AND
 WATTAGE.
  
 FOR EXAMPLE: INTERIOR LIGHT FIXTURES SHALL INCLUDE ALL
 AREAS. BASED ON THE IDR, IT ONLY LIST TWO DIFFERENT
 TYPE OF FIXTURES. BASED ON THE PLANS AND THE FIXTURE
 LEGEND THIS IS NOT THE CASE.
  
 FOR EXAMPLE: FIXTURES NEED TO BE SPECIFIC. MOST
 FIXTURES STATE *TBD* WHICH THE VA RATING CAN NOT BE
 VERIFIED. PLEASE SELECT SPECIFIC FIXTURES. THESE MAY
 ALWAYS BE REVISED AT A LATER DATE IF A PRODUCT CHANGES.
 THE GOAL IS AT LEAST TO MEET THE MINIMUM CODES.
 *D* FIXTURES ARE SHOWN ON PLANS HOWEVER HAVE DIFFERENT
 SYMBOLS. WHEN LOOKING AT THE SYMBOL LEGEND YOU WILL SEE
 EACH OF THESE ARE ACTUALLY DIFFERENT. ONE IS 58VA AND
 THE OTHER 29 VA.
  
  
 *** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT TO
 HELP. THESE MAY NOT BE ALL ITEMS. IT IS IMPORTANT TO
 FIGURE HOW CALCULATIONS WILL BE DONE FOR EACH SPACE OR
 AS PART OF THE BUILDING.
 PLEAS BE SURE TO GO OVER AND CALL WITH ANY COMMENTS OR
 QUESTIONS FOR COORDINATION.
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE CONTROLS
 REQUIRED FOR CONFERENCE ROOM. ( NOTED ON PREVIOUS
 REVIEW)
  
 5) NOTE: BASED ON A COMPLETE REVISED ELECTRICAL RISER,
 PLEASE SEE 230.70. THERE ARE UNPROTECTED CONDUCTORS
 INSIDE THE BUILDING WHICH IS NOT PERMITTED. THE CODE
 SECTION GIVEN DOES NOT GIVE AN AMOUNT PERMITTED.
 THE OLD PALM BEACH COUNTY AND CITY OF WEST PALM BEACH
 TECHNICAL AMENDMENTS PERMITTED UP TO 8FT, HOWEVER AS
 THE OLDER CODE CHANGED THE TECHNICAL AMENDMENTS WENT
 AWAY. SOME MUNICIPALITIES DO NOT PERMIT ANY UNPROTECTED
 CONDUCTORS INSIDE THE BUILDING.
 THE AMOUNT AS SHOWN ON PLANS IS OVER. PLEASE ADJUST
 DESIGN.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2009-02-06 17:00:40REVIEW TO CONTINUE. REVIEW WILL GO INTO A FAILED STATUS
 ONCE COMPLETE. SOME NOTES FROM PREVIOUS REVIEW AND
 MEETING STILL NEED TO BE ADDRESSED.