Plan Review Notes
Plan Review Notes For Permit 08090247
Permit Number 08090247
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-15 13:37:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 2. SUBMIT MANUF. SPECIFICTIONS FOR THE BUBBLER SHOWING
 CONFORMANCE WITH ASME A112.19.1M, ASME A112.19.2M OR
 ASME A112.19.9M AS WELL AS NSF61 SECTION 9. SECTION
 410.
  
 3. SHT A-1.02 A WASH MACHINE CONNECTION IS REQUIRED IN
 THE UNIT WITH ROOMS 201, 202 & 203. TABLE 403.1.
  
 4. SHT A-5.01 DETAIL (1), LAV SHALL BE MINIMUM 15" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE
 CENTERED ON THE REQUIRED 30" WIDTH OF THE CLEAR FLOOR
 SPACE. SECTION 11-4.19.3 & FIGURE 32.
  
 5. SHT A-5.01 DETAIL (2), THE DISPENSER SHALL BE
 MINIMUM 19" OFF THE FLOOR TO THE CENTERLINE. DETAIL
 SHOWS 17" TO CENTERLINE. SECTION 11-4.19.6 & FIGURE
 29(B).
  
 6. SHT A-5.01 SHOW COMPLIANCE WITH SECTION 11-4.19.5
 FAUCETS.
  
 7. SHT A-5.01 DETAIL (4), INDICATES "OPTIONAL CUP
 HOLDER". IF THE CUP HOLDER IS NOT REQUIRED, THEN SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 8. SHT P-1.01 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUSINESS OCCUPANCY. SECTION 608.13.3.
  
 9. SHT P-1.02 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE CLEANOUT SHOWN ON THE RISER
 DIAGRAM DOWNSTREAM OF THE LAST TWO 3" RISERS IS NOT
 SHOWN ON THE FLOOR PLAN. -- RISER DOES NOT SHOW THE
 VENT THRU THE ROOF FOR THE FIXTURES ON THE FIRST FLOOR.
 PLEASE CORRELATE. SECTIONS 106.1.1, 708.3.3 & 903.3.
  
 10. SHT P-1.02 NOTE FOR WATER HEATER AT THE TOP OF THE
 SHEET IS NOT LEGIBLE. PLEASE CLARIFY. SECTION 106.1.1.
  
 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS (REQD BY
 SECTION 604.9) ETC. SECTION 105.3.5.1.3 & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved