Date |
Text |
2008-09-15 13:37:04 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| |
| 2. SUBMIT MANUF. SPECIFICTIONS FOR THE BUBBLER SHOWING |
| CONFORMANCE WITH ASME A112.19.1M, ASME A112.19.2M OR |
| ASME A112.19.9M AS WELL AS NSF61 SECTION 9. SECTION |
| 410. |
| |
| 3. SHT A-1.02 A WASH MACHINE CONNECTION IS REQUIRED IN |
| THE UNIT WITH ROOMS 201, 202 & 203. TABLE 403.1. |
| |
| 4. SHT A-5.01 DETAIL (1), LAV SHALL BE MINIMUM 15" OFF |
| THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE |
| CENTERED ON THE REQUIRED 30" WIDTH OF THE CLEAR FLOOR |
| SPACE. SECTION 11-4.19.3 & FIGURE 32. |
| |
| 5. SHT A-5.01 DETAIL (2), THE DISPENSER SHALL BE |
| MINIMUM 19" OFF THE FLOOR TO THE CENTERLINE. DETAIL |
| SHOWS 17" TO CENTERLINE. SECTION 11-4.19.6 & FIGURE |
| 29(B). |
| |
| 6. SHT A-5.01 SHOW COMPLIANCE WITH SECTION 11-4.19.5 |
| FAUCETS. |
| |
| 7. SHT A-5.01 DETAIL (4), INDICATES "OPTIONAL CUP |
| HOLDER". IF THE CUP HOLDER IS NOT REQUIRED, THEN SHOW |
| COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| |
| 8. SHT P-1.01 AN RPZV BACKFLOW IS REQUIRED ON THE WATER |
| SERVICE TO THE BUSINESS OCCUPANCY. SECTION 608.13.3. |
| |
| 9. SHT P-1.02 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN. THE CLEANOUT SHOWN ON THE RISER |
| DIAGRAM DOWNSTREAM OF THE LAST TWO 3" RISERS IS NOT |
| SHOWN ON THE FLOOR PLAN. -- RISER DOES NOT SHOW THE |
| VENT THRU THE ROOF FOR THE FIXTURES ON THE FIRST FLOOR. |
| PLEASE CORRELATE. SECTIONS 106.1.1, 708.3.3 & 903.3. |
| |
| 10. SHT P-1.02 NOTE FOR WATER HEATER AT THE TOP OF THE |
| SHEET IS NOT LEGIBLE. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL |
| PIPE SIZES, VALVES, WATER HAMMER ARRESTORS (REQD BY |
| SECTION 604.9) ETC. SECTION 105.3.5.1.3 & 601.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |