Date |
Text |
2008-10-17 13:44:23 | *****DENIED***** |
| |
| 01. THE COMPLETE ADDRESS SHALL BE IN THE TITLE BLOCK OF |
| EACH SUBMITTED PLAN SHEET. BE ADVISED THAT THIS IS |
| NORTH ROSEMARY AVENUE, NOT JUST ROSEMARY AVENUE AS |
| SHOWN ON THE SUBMITTED SHEETS. |
| |
| 02. ON SHEET L-1.01 PICTORIAL CAPTION 1 AND SHEET |
| C-0.01, C-0.03, A-0.01, AD-3.01 (EAST ELEVATION) & |
| A-3.02 (EAST ELEVATION), ROSEMARY IS IS INCORRECTLY |
| LABELED AS A STREET AND NOT AN AVENUE. |
| |
| 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 04. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE |
| VICINITY THEREOF (INCLUDING ROADS, ALLEYS, FIRE LANES) |
| . |
| |
| 05. ON SHEET A-0.00, THE PHONE NUMBER FOR WEST PALM |
| BEACH FIRE RESCUE IS 561-804-4700. |
| |
| 06. EXPLAIN THE PURPOSE OF THE EXIT SIGN LIGHTS SHOWN |
| ON SHEET A0.00 IN AREAS MARKED 107-1 & 107-2 AS |
| INDICATED ON SHEET A-1.01. |
| |
| 07. PROVIDE THE PRESCRIPTIVE STRENGTHS FOR THE |
| GUARDRAILS/HANDRAILS. |
| |
| 08. STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES. IT |
| APPEARS THAT THE WEST ELEVATION STAIRS HAVE HANDRAILS |
| ON ONE SIDE. |
| |
| 09. OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED BE TO |
| MINIMIZE WATER ACCUMULATION ON THEIR SURFACES. |
| |
| 10. THE WIDTH OF STAIRS SHALL COMPY WITH NFPA 101 - |
| 7.2.2.2.1 - 2003 EDITION. |
| |
| 11. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01), |
| EXPLAIN WHY THE MECHANICAL ROOM (#111-1) AND STORAGE |
| ROOM (#113-1) DOORS ARE NOT FIRE RATED. |
| |
| 12. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01), |
| WHY IS EXTERIOR HALLWAY DOOR 204-1 FIRE-RATED BUT NOT |
| 204-2 ? |
| |
| 13. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01), |
| WHY ARE INTERIOR HALLWAY (COMMON CORRIDOR) DOORS 205-1 |
| AND 210-1 NOT FIRE RATED. |
| |
| 14. DOORS AND WINDOWS REQUIRED TO HAVE A FIRE RATING |
| SHALL COMPLY WITH NFPA 80. |
| |
| 15. IT IS SHOWN THAT THIS BUILDING WILL HAVE A FIRE |
| ALARM SYSTEM. EXPLAIN WHAT SMOKE SENSORS ARE IN |
| RELATION TO SMOKE DETECTORS AND/OR SMOKE ALARMS. BE |
| ADVISE THAT SMOKE DETECTORS (SD) ARE TIED INTO THE |
| BUILDING'S FIRE ALARM SYSTEM WHEREAS SMOKE ALARMS (SA) |
| ALERT THE OCCUPANT(S) OF THE DWELLING UNIT ONLY. |
| |
| 16. IF THE BUILDING IS TO BE EQUIPPED WITH A FIRE ALARM |
| SYSTEM, SMOKE DETECTORS (SD) ARE REQUIRED IN THE 2ND |
| FLOOR HALLWAY (COMMON CORRIDOR) . |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE/HOW THE ITEMS WERE ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |