Plan Review Notes
Plan Review Notes For Permit 08090247
Permit Number 08090247
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-10-17 13:44:23*****DENIED*****
  
 01. THE COMPLETE ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET. BE ADVISED THAT THIS IS
 NORTH ROSEMARY AVENUE, NOT JUST ROSEMARY AVENUE AS
 SHOWN ON THE SUBMITTED SHEETS.
  
 02. ON SHEET L-1.01 PICTORIAL CAPTION 1 AND SHEET
 C-0.01, C-0.03, A-0.01, AD-3.01 (EAST ELEVATION) &
 A-3.02 (EAST ELEVATION), ROSEMARY IS IS INCORRECTLY
 LABELED AS A STREET AND NOT AN AVENUE.
  
 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING ROADS, ALLEYS, FIRE LANES)
 .
  
 05. ON SHEET A-0.00, THE PHONE NUMBER FOR WEST PALM
 BEACH FIRE RESCUE IS 561-804-4700.
  
 06. EXPLAIN THE PURPOSE OF THE EXIT SIGN LIGHTS SHOWN
 ON SHEET A0.00 IN AREAS MARKED 107-1 & 107-2 AS
 INDICATED ON SHEET A-1.01.
  
 07. PROVIDE THE PRESCRIPTIVE STRENGTHS FOR THE
 GUARDRAILS/HANDRAILS.
  
 08. STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES. IT
 APPEARS THAT THE WEST ELEVATION STAIRS HAVE HANDRAILS
 ON ONE SIDE.
  
 09. OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED BE TO
 MINIMIZE WATER ACCUMULATION ON THEIR SURFACES.
  
 10. THE WIDTH OF STAIRS SHALL COMPY WITH NFPA 101 -
 7.2.2.2.1 - 2003 EDITION.
  
 11. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01),
 EXPLAIN WHY THE MECHANICAL ROOM (#111-1) AND STORAGE
 ROOM (#113-1) DOORS ARE NOT FIRE RATED.
  
 12. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01),
 WHY IS EXTERIOR HALLWAY DOOR 204-1 FIRE-RATED BUT NOT
 204-2 ?
  
 13. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01),
 WHY ARE INTERIOR HALLWAY (COMMON CORRIDOR) DOORS 205-1
 AND 210-1 NOT FIRE RATED.
  
 14. DOORS AND WINDOWS REQUIRED TO HAVE A FIRE RATING
 SHALL COMPLY WITH NFPA 80.
  
 15. IT IS SHOWN THAT THIS BUILDING WILL HAVE A FIRE
 ALARM SYSTEM. EXPLAIN WHAT SMOKE SENSORS ARE IN
 RELATION TO SMOKE DETECTORS AND/OR SMOKE ALARMS. BE
 ADVISE THAT SMOKE DETECTORS (SD) ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM WHEREAS SMOKE ALARMS (SA)
 ALERT THE OCCUPANT(S) OF THE DWELLING UNIT ONLY.
  
 16. IF THE BUILDING IS TO BE EQUIPPED WITH A FIRE ALARM
 SYSTEM, SMOKE DETECTORS (SD) ARE REQUIRED IN THE 2ND
 FLOOR HALLWAY (COMMON CORRIDOR) .
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE ITEMS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722