Plan Review Notes
Plan Review Notes For Permit 08090247
Permit Number 08090247
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-06 11:43:07 
 ** DENIED REVIEW **
  
 *** PLEASE SEE COVER SHEET OF PLANS CALL FOR PLANS
 BEING 95% COMPLETE. PLEASE SUBMIT 100% PLANS.
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED ENERGY COMPLIANCE
 CALCULATIONS PER 13-101.1, 13-415.2,
 13-415.2.ABC.1.1,.1.2, .1.3.
 PLEASE SEE THE METHOD *A* AS SUBMITTED IS FOR A WHOLE
 BUILDING WHICH THIS IS NOT BASED ON USE AND OCCUPANCY.
 PLEASE SEE DEFINITIONS IN SECTION 202 FOR SEPARATIONS
 ETC.
 PLEASE KNOW IN ANY CASE THE CALCULATIONS AS SUBMITTED
 ARE NOT COMPLETE AND DO NOT COORDINATE WITH THE
 SUBMITTED PLANS. SOME EXAMPLES WILL BE GIVEN. THE INPUT
 DATA REPORT WILL BE NOTED AS IDR BELOW.
  
 EXAMPLE: THERE IS NO EXTERIOR LIGHTING IN THE IDR YET
 THE PLANS CLEARLY SHOW EXTERIOR FIXTURES.
 EXAMPLE: THERE ARE NO WATER HEATERS IN THE IDR, YET
 PLANS INDICATE ELECTRIC WATER HEATER. ( OFFICE SPACE)
 EXAMPLE: THERE ARE OTHER COMPONENTS ON PLANS WHICH ARE
 NOT PART OF THE IDR. PLEASE SEE COMMENTS FROM OTHER
 TRADES.
 EXAMPLE: PLEASE SEE THE NUMBER, TYPE, WATTAGES OF THE
 INTERIOR LIGHTING BASED ON THE FIXTURE SON PLANS AND
 THE FIXTURE LEGEND DOES NOT COORDINATE.
 PLEASE BE SURE THE FIXTURE LEGEND IS SPECIFIC, COMPLETE
 AND COORDINATE ALL ON PLANS WITH THE IDR.
  
 2) NOTE: PLEASE SEE FBC 3006.2 FOR MISSING EQUIPMENT IN
 ELEVATOR MACHINE ROOM. THIS WILL AFFECT THE ELECTRICAL
 PLANS.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SEPARATE
 SPACES WHICH DO REQUIRED AUTOMATED LIGHTING CONTROLS.
 THE IDR INDICATES OCCUPANCY SENSORS YET THE PLANS DO
 NOT SEEM TO INDICATE ANY.
 PLEASE COMPLETE PLANS FOR MISSING DEVICES AS REQUIRED.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 EXTERIOR LIGHTING CONTROLS. THERE ARE TWO METHODS FOR
 CONTROLLING EXTERIOR LIGHTING. THE CONTROLS ON SHEET
 E-301 DOES NOT COMPLETE ALL THAT IS REQUIRED. PLEASE
 KEEP IN MIND IF USING AN OVER RIDE AS SHOWN THIS DEVICE
 MUST HAVE AN OVER RIDE OF SOME KIND WHICH WILL NOT
 PERMIT THE LIGHTING TO BE ON DURING DAY LIGHT HOURS.
  
 5) NOTE: PLEASE VERIFY THE SIGN CIRCUIT REQUIRED PER
 600.5
  
 6) NOTE: PLEASE SEE NFPA-72 DEFINITIONS. THE PLANS CALL
 FOR A *S* AND THE *S* ON THE SYMBOL LEGEND INDICATES A
 SMOKE DETECTOR INSIDE AND OUTSIDE EACH SLEEPING ROOM. A
 SMOKE DETECTOR BY DEFINITION IS A DEVICE WHICH WILL
 DETECT AND NOT SOUND AN ALARM. A SMOKE ALARM IS A
 DEVICE WHICH WILL DETECT AND SOUND THE ALARM. THE
 SYMBOL LEGEND SEEMS TO LEND TO A SMOKE ALARM BY THE
 DESCRIPTION. PLEASE VERIFY AND ADJUST.
 IF INSTALLING SMOKE DETECTORS, PLEASE COMPLETE PLANS
 WITH THE SYSTEM. (PANEL, SOUNDING DEVICES ETC).
  
 7) NOTE: PLEASE SEE UNIT *C* WHICH WILL REQUIRE ARC
 FAULT FOR ALL CIRCUITS IN AREA USED FOR SLEEPING AND
 LIVING ROOM. AS THESE ARE ONE IN THE SAME AFCI
 PROTECTION IS REQUIRED. 210.12
  
 8) NOTE: PLEASE SEE UNITS A AND B AS THESE ARE MISSING
 RECEPTACLES PER 210.52B1, 210.11C1, 210.52C3, 4. (ROOMS
 206,211
  
 9) NOTE: PLEASE SEE UNITS A AND B FOR MISSING WALL
 RECEPTACLES PER 210.52. THESE ARE ABOUT THE SAME AREAS
 AS NOTED ABOVE IN NOTE #8.
  
 10) NOTE: PLEASE SEE 422.13 AS WATER HEATERS ARE NOW
 CONSIDERED CONTINUOUS LOADS UNDER THE 2005 NEC. PLEASE
 ADJUST LOAD CALCULATIONS FOR THESE LOADS AT 125%.
  
 11) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1,.2.2
 STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER NORMAL
 AND IS PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY
 POWER.
 PLEASE PROVIDE LEVELS FOR ALL EGRESS AREAS.
 FAC 61G15-33.004
 FBC 106.1.1, FOR ADDITIONAL INFORMATION.
  
 12) NOTE: PLEASE INDICATE THE SIZE OF THE GUTTER SO
 COMPLIANCE WITH FILL CAN BE VERIFIED.
 366.22
  
 13) NOTE: BASED ON THE SITE PLANS AND SURVEY SUBMITTED
 THE ELECTRICAL SERVICE MAY NOT BE LOCATED ON THE SIDE
 OF THE BUILDING AS SHOWN. THE OVER HEAD SERVICE DOES
 MEET MINIMUM CLEARANCE FROM OPENINGS PER 23.24.
 THE ELECTRICAL SERVICE LOCATION DOES NOT MEET 110.26
 FOR WORKING CLEARANCES REQUIRED.
  
 14) NOTE: BASED ON MANY ASPECTS OF THE SCOPE OF WORK
 STILL IN NEED FOR CODE COMPLIANCE FROM THIS TRADE AS
 WELL AS OTHER TRADES THER MAY VERY WELL BE NEW COMMENTS
 ON THE NEXT REVIEW.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  