Date |
Text |
2008-10-06 11:43:07 | |
| ** DENIED REVIEW ** |
| |
| *** PLEASE SEE COVER SHEET OF PLANS CALL FOR PLANS |
| BEING 95% COMPLETE. PLEASE SUBMIT 100% PLANS. |
| |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETED ENERGY COMPLIANCE |
| CALCULATIONS PER 13-101.1, 13-415.2, |
| 13-415.2.ABC.1.1,.1.2, .1.3. |
| PLEASE SEE THE METHOD *A* AS SUBMITTED IS FOR A WHOLE |
| BUILDING WHICH THIS IS NOT BASED ON USE AND OCCUPANCY. |
| PLEASE SEE DEFINITIONS IN SECTION 202 FOR SEPARATIONS |
| ETC. |
| PLEASE KNOW IN ANY CASE THE CALCULATIONS AS SUBMITTED |
| ARE NOT COMPLETE AND DO NOT COORDINATE WITH THE |
| SUBMITTED PLANS. SOME EXAMPLES WILL BE GIVEN. THE INPUT |
| DATA REPORT WILL BE NOTED AS IDR BELOW. |
| |
| EXAMPLE: THERE IS NO EXTERIOR LIGHTING IN THE IDR YET |
| THE PLANS CLEARLY SHOW EXTERIOR FIXTURES. |
| EXAMPLE: THERE ARE NO WATER HEATERS IN THE IDR, YET |
| PLANS INDICATE ELECTRIC WATER HEATER. ( OFFICE SPACE) |
| EXAMPLE: THERE ARE OTHER COMPONENTS ON PLANS WHICH ARE |
| NOT PART OF THE IDR. PLEASE SEE COMMENTS FROM OTHER |
| TRADES. |
| EXAMPLE: PLEASE SEE THE NUMBER, TYPE, WATTAGES OF THE |
| INTERIOR LIGHTING BASED ON THE FIXTURE SON PLANS AND |
| THE FIXTURE LEGEND DOES NOT COORDINATE. |
| PLEASE BE SURE THE FIXTURE LEGEND IS SPECIFIC, COMPLETE |
| AND COORDINATE ALL ON PLANS WITH THE IDR. |
| |
| 2) NOTE: PLEASE SEE FBC 3006.2 FOR MISSING EQUIPMENT IN |
| ELEVATOR MACHINE ROOM. THIS WILL AFFECT THE ELECTRICAL |
| PLANS. |
| |
| 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SEPARATE |
| SPACES WHICH DO REQUIRED AUTOMATED LIGHTING CONTROLS. |
| THE IDR INDICATES OCCUPANCY SENSORS YET THE PLANS DO |
| NOT SEEM TO INDICATE ANY. |
| PLEASE COMPLETE PLANS FOR MISSING DEVICES AS REQUIRED. |
| |
| 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED |
| EXTERIOR LIGHTING CONTROLS. THERE ARE TWO METHODS FOR |
| CONTROLLING EXTERIOR LIGHTING. THE CONTROLS ON SHEET |
| E-301 DOES NOT COMPLETE ALL THAT IS REQUIRED. PLEASE |
| KEEP IN MIND IF USING AN OVER RIDE AS SHOWN THIS DEVICE |
| MUST HAVE AN OVER RIDE OF SOME KIND WHICH WILL NOT |
| PERMIT THE LIGHTING TO BE ON DURING DAY LIGHT HOURS. |
| |
| 5) NOTE: PLEASE VERIFY THE SIGN CIRCUIT REQUIRED PER |
| 600.5 |
| |
| 6) NOTE: PLEASE SEE NFPA-72 DEFINITIONS. THE PLANS CALL |
| FOR A *S* AND THE *S* ON THE SYMBOL LEGEND INDICATES A |
| SMOKE DETECTOR INSIDE AND OUTSIDE EACH SLEEPING ROOM. A |
| SMOKE DETECTOR BY DEFINITION IS A DEVICE WHICH WILL |
| DETECT AND NOT SOUND AN ALARM. A SMOKE ALARM IS A |
| DEVICE WHICH WILL DETECT AND SOUND THE ALARM. THE |
| SYMBOL LEGEND SEEMS TO LEND TO A SMOKE ALARM BY THE |
| DESCRIPTION. PLEASE VERIFY AND ADJUST. |
| IF INSTALLING SMOKE DETECTORS, PLEASE COMPLETE PLANS |
| WITH THE SYSTEM. (PANEL, SOUNDING DEVICES ETC). |
| |
| 7) NOTE: PLEASE SEE UNIT *C* WHICH WILL REQUIRE ARC |
| FAULT FOR ALL CIRCUITS IN AREA USED FOR SLEEPING AND |
| LIVING ROOM. AS THESE ARE ONE IN THE SAME AFCI |
| PROTECTION IS REQUIRED. 210.12 |
| |
| 8) NOTE: PLEASE SEE UNITS A AND B AS THESE ARE MISSING |
| RECEPTACLES PER 210.52B1, 210.11C1, 210.52C3, 4. (ROOMS |
| 206,211 |
| |
| 9) NOTE: PLEASE SEE UNITS A AND B FOR MISSING WALL |
| RECEPTACLES PER 210.52. THESE ARE ABOUT THE SAME AREAS |
| AS NOTED ABOVE IN NOTE #8. |
| |
| 10) NOTE: PLEASE SEE 422.13 AS WATER HEATERS ARE NOW |
| CONSIDERED CONTINUOUS LOADS UNDER THE 2005 NEC. PLEASE |
| ADJUST LOAD CALCULATIONS FOR THESE LOADS AT 125%. |
| |
| 11) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR |
| EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1,.2.2 |
| STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER NORMAL |
| AND IS PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY |
| POWER. |
| PLEASE PROVIDE LEVELS FOR ALL EGRESS AREAS. |
| FAC 61G15-33.004 |
| FBC 106.1.1, FOR ADDITIONAL INFORMATION. |
| |
| 12) NOTE: PLEASE INDICATE THE SIZE OF THE GUTTER SO |
| COMPLIANCE WITH FILL CAN BE VERIFIED. |
| 366.22 |
| |
| 13) NOTE: BASED ON THE SITE PLANS AND SURVEY SUBMITTED |
| THE ELECTRICAL SERVICE MAY NOT BE LOCATED ON THE SIDE |
| OF THE BUILDING AS SHOWN. THE OVER HEAD SERVICE DOES |
| MEET MINIMUM CLEARANCE FROM OPENINGS PER 23.24. |
| THE ELECTRICAL SERVICE LOCATION DOES NOT MEET 110.26 |
| FOR WORKING CLEARANCES REQUIRED. |
| |
| 14) NOTE: BASED ON MANY ASPECTS OF THE SCOPE OF WORK |
| STILL IN NEED FOR CODE COMPLIANCE FROM THIS TRADE AS |
| WELL AS OTHER TRADES THER MAY VERY WELL BE NEW COMMENTS |
| ON THE NEXT REVIEW. |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |