2008-10-02 12:14:18 | BUILDING PLAN REVIEW |
| PERMIT: 08090247 |
| ADD: 501 N ROSEMARY AVE |
| CONT: NUJAK DEVELOPMENT |
| TEL: (863)686-1565 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 2) SHEET A0.00 CODE ANALYSIS INDICATES THIS BUILDING IS |
| TO BE A TYPE III-B BUILDING AND A LEVEL III ALTERATION, |
| MIXED OCCUPANCY WITH A BUSINESS OCCUPANCY FIRST FLOOR |
| AND R-2 RESIDENCY SECOND FLOOR. |
| SHEET A-1.01 ALSO INDICATES THE PROPERTY LINE ON THE |
| WEST SIDE OF THE PROPERTY TO BE APPROXIMATELY 3'-0" |
| AWAY. THE SURVEY PROVIDES A DIMENSION AT THE NORTHWEST |
| CORNER OF THE BUILDING INDICATING |
| A DISTANCE OF 2.90' AWAY FROM THE PROPERTY LINE. LEVEL |
| III ALTERATIONS SECTION 705.1 THE MEANS OF EGRESS SHALL |
| COMPLY WITH THE REQUIREMENTS OF SECTION 605 EXCEPT AS |
| MODIFIED IN SECTIONS 705.2 AND 705.3. UNDER LEVEL II |
| SECTION 605.1 THE REQUIREMENTS OF THIS SECTION SHALL BE |
| LIMITED TO WORK AREAS THAT INCLUDE EXITS OR CORRIDORS |
| SHARED BY MORE THAN ONE TENANT WITHIN THE WORK AREA IN |
| WHICH LEVEL 2 ALTERATIONS ARE BEING PREFORMED, AND |
| WHERE SPECIFIED THEY SHALL APPLY THROUGHOUT THE FLOOR |
| ON WHICH THE WORK AREAS ARE LOCATED OR OTHERWISE BEYOND |
| THE WORK AREA. |
| |
| 2A) WITH THIS BEING A LEVEL III ALTERATION THE EXTERIOR |
| STAIRWAY BEING REPAIRED AND RELOCATED BASICALLY IN THE |
| SAME LOCATION , PLEASE PROVIDE COMPLIANCE WITH 1022.5 . |
| EXTERIOR EXIT STAIRWAYS SHALL BE LOCATED IN ACCORDANCE |
| WITH SECTION 1023.3. |
| 1023.3 EXIT DISCHARGE LOCATION. |
| EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE |
| LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT |
| LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS |
| THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE |
| PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE |
| SEPARATION DISTANCE. |
| |
| 2B) THE SECOND ISSUE WITH NOT KNOWING THE DISTANCE FROM |
| THE PROPERTY LINE AT THE SECOND FLOOR DOOR OPENING IS |
| IN TABLE 704.8 FOR UNPROTECTED OPENINGS 0-3-0? ZERO |
| OPENINGS IN THE WALL LINE. |
| |
| 2C) SHEET A-1.03 INDICATE A 5?X5? DOWNSPOUT, THE SITE |
| PLAN INDICATES A 6?-0? HIGH SECURITY FENCE ALONG THE |
| SAME PROPERTY LINE AND THE SURVEY INDICATES FROM THE |
| BUILDING TO PROPERTY LINE A DISTANCE OF 2.90?. HOW WILL |
| SECTION 1009.1EXCEPTION# 1 REQUIRING A 36? WIDE STAIR? |
| |
| 2D) THE OTHER ISSUE IS WITH THE 5?X5? DOWNSPOUT, HOW |
| WILL SECTION 1009.11.7 PROJECTIONS INTO THE REQUIRED |
| WIDTH AT EACH HANDRAIL SHALL NOT EXCEED 4.5 INCHES AT |
| OR BELOW THE HANDRAIL HEIGHT. NOTE HANDRAILS ARE TO BE |
| CONTINUOUS SEE 1009.11.4 CONTINUITY. |
| |
| 2E) THE PLANS FAIL TO INDICATE HANDRAILS AT EACH SIDE |
| OF THE STAIRS. 1009.11. |
| |
| 3) SHEET A-1.01 DOOR# 115-1 MACHINE ROOM, AGAIN THIS |
| NEW ADDITION WALL LINES UP WITH THE EXISTING WALL THAT |
| IS 2.90? FROM THE PROPERTY LINE. TABLE 704.8 THAT DOES |
| NOT ALLOW OPENINGS UNTIL GRATER THAN 5.0? FROM THE |
| PROPERTY LINE FOR UNPROTECTED OPENINGS. ALSO NOTE THIS |
| DOOR NEEDS TO BE A 1-HR RATED DOOR AS TO 3006.4. THE |
| ONE HR RATING WOULD ALLOW UNDER PROTECTED OPENINGS 15% |
| ALLOWABLE OPENINGS AT DISTANCES OF 3?-0? AND GREATER. |
| THE OTHER ISSUE IS THE DOOR SWING IS OVER THE ALLOWABLE |
| EGRESS PATH. 1008.1.8.8. |
| |
| 4) SHEET A-1.02 WINDOW OPENING 18A IS UNPROTECTED, IS |
| AGAIN LESS THAN 5?-0? FROM THE PROPERTY LINE AND NOT |
| ALLOWED TABLE 704.8. |
| |
| 5) SHEET A-3.01 WEST ELEVATION INDICATES A LOUVERS ON |
| THIS ELEVATION AGAIN UNPROTECTED OPENINGS WOULD NOT BE |
| ALLOWED WITH UNPROTECTED OPENINGS, PLEASE SEE TABLE |
| 704.8 FOR UNPROTECTED OPENINGS AND FOR PROTECTED |
| OPENINGS. |
| |
| 6) THIS BUILDING DOES NOT PROVIDE ANY INFORMATION AS TO |
| FIRE SPRINKLERS, SO IT IS ASSUMED TO BE AN |
| UN-SPRINKLERED BUILDING. WITH THE R-2 OCCUPANCY AND THE |
| ADDITION OF THE ELEVATOR THE REQUIREMENT FOR A AREA OF |
| RESCUE ASSISTANCE NECESSARY. PLEASE REVIEW ALL THE |
| REQUIREMENTS OF 11-4.3.11(1-3). |
| |
| 6A) PLEASE INDICATE IF THE AREA OF RESCUE ASSISTANCE |
| WILL BE LOCATED ON THE INTERIOR OF THE BUILDING OR IF |
| IT WILL BE LOCATED ON THE EXTERIOR 2ND FLOOR LANDING OF |
| THE BUILDING, AND NEEDING TO HAVE FIRE RATED WINDOWS |
| AND DOORS. IN EITHER CASE PLEASE PROVIDE THE REQUIRED |
| CLEAR FLOOR SPACE REQUIRED FOR THE AREA OF RESCUE |
| ASSISTANCE AND THE MEANS OF EGRESS |
| |
| 6B) PLEASE ALSO TAKE NOTE OF THE REQUIRED 48? CLEAR |
| BETWEEN HANDRAILS, |
| 11-4.3.11.3. |
| |
| 7) SHEET A-1.02 THE SECOND STORY LANDING INDICATES A |
| SCUPPER LOCATED AT FLOOR LEVEL TO DRAIN WATER FROM THE |
| LANDING. THE WATER THAT DRAINS FROM THE SCUPPER LANDS |
| DIRECTLY ON TO THE STAIRS BELOW, PLEASE PROVIDE |
| COMPLIANCE WITH 1009.5.2 OUTDOOR CONDITIONS. |
| |
| 8) SHEET A-1.03 ROOF PLAN INDICATES ?GAF LIBERTY OR |
| APPROVED EQUAL?, 106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 9) SHEET A-4.01 S-3.02 BOTH INDICATE A NEW SECOND STORY |
| EPICORE CONCRETE PRE-ENGINEERED FLOOR SYSTEM, PLEASE |
| PROVIDE ADDITIONAL INFORMATION ARE SHOP DRAWINGS BEING |
| CREATED, INDICATING OF SPANS, LOADS TO BE IMPOSED, |
| REINFORCING AND SHORING. 1905, 1907. |
| |
| 10) PLEASE PROVIDE HOURLY RATING FOR THE EPICORE |
| CONCRETE FLOOR SYSTEM, A 2HR FIRE RATING WILL BE |
| REQUIRED BETWEEN THE R-2 OCCUPANCY AND BUSINESS |
| OCCUPANCY BELOW. SEE TABLE 302.3.2& 712.4, ALSO PROVIDE |
| FIRE RESISTANCE RATED ASSEMBLIES FOR THE PENETRATION OF |
| THE SECOND STORY FLOOR ASSEMBLIES, 712.4.1. |
| |
| 11) PLANS FAIL TO PROVIDE FLOOR/CEILING ASSEMBLIES |
| SOUND RATING AS REQUIRED BY 1207.3. STRUCTURE-BORNE |
| SOUND. FLOOR/ CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL |
| HAVE AN IMPACT INSULATION CLASS RATING OF NOT LESS THAN |
| 50(45IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. |
| |
| 12) SHEET A-1.02 WALL TYPE# 8 FAILS TO PROVIDE A STC |
| RATING OF 50, 1207.2 AIR-BORNE SOUND. |
| |
| 13) SHEET A-2.01 SECOND STORY CORRIDOR REFLECTED |
| CEILING PLAN DOES NOT INDICATE THE EXIT SIGNS , 1006.3. |
| |
| 14) PLANS S-1.01 INDICATE THE USE OF HELICAL PIER UNDER |
| PINNING OF FOUNDATION, PLEASE PROVIDE SOILS REPORT . |
| 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| THROUGH 1802.6 . |
| |
| 15) SHEET S-0.01 IS USING THE WRONG VERSION OF THE |
| ASCE-7-05. |
| 2004 FBC 1609.1.1 & CHAPTER 35 REFERENCED STANDARDS |
| RECOGNIZES ASCE 7-02 . ALSO 1603.1.4 WIND DESIGN DATA. |
| |
| 16) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS:\ |
| 16A) SINGLE HUNG WINDOWS |
| 16B) FIXED, STOREFRONT |
| 16C) MULLIONS |
| 16D) EXTERIOR GLAZED DOORS |
| 16E) EXTERIOR METAL DOORS |
| 16F) EXTERIOR LOUVER DOORS |
| 16G) WALL LOUVERS |
| 16H) LINTELS |
| 16I) ROOFING ASSEMBLIES, FLAT ROOF, UNDERLAYMENT?S, |
| TILE AND ADHESIVES |
| |
| 17) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 18) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 19) THE INPUT DATA REPORT FROM THE ENERGY CALCS DOES |
| NOT MATCH THE PLANS, THE COUNT ON THE WINDOWS AND THE |
| SQUARE FOOTAGE ARE OFF AND THE DOOR TYPE AND DOOR COUNT |
| DOES NOT MATCH THAT OF THE PLANS. THERE ARE A TOTAL OF |
| 5 DOORS THAT LEAD INTO THE BUSINESS OFFICE PLEASE |
| CORRECT. MISSING NORTH DOOR 101-2 AND PAIR OF DOORS |
| 102-1. |
| |
| 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC |
| |
| |