2008-10-02 12:14:18BUILDING PLAN REVIEW
 PERMIT: 08090247
 ADD: 501 N ROSEMARY AVE
 CONT: NUJAK DEVELOPMENT
 TEL: (863)686-1565
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) SHEET A0.00 CODE ANALYSIS INDICATES THIS BUILDING IS
 TO BE A TYPE III-B BUILDING AND A LEVEL III ALTERATION,
 MIXED OCCUPANCY WITH A BUSINESS OCCUPANCY FIRST FLOOR
 AND R-2 RESIDENCY SECOND FLOOR.
 SHEET A-1.01 ALSO INDICATES THE PROPERTY LINE ON THE
 WEST SIDE OF THE PROPERTY TO BE APPROXIMATELY 3'-0"
 AWAY. THE SURVEY PROVIDES A DIMENSION AT THE NORTHWEST
 CORNER OF THE BUILDING INDICATING
 A DISTANCE OF 2.90' AWAY FROM THE PROPERTY LINE. LEVEL
 III ALTERATIONS SECTION 705.1 THE MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 605 EXCEPT AS
 MODIFIED IN SECTIONS 705.2 AND 705.3. UNDER LEVEL II
 SECTION 605.1 THE REQUIREMENTS OF THIS SECTION SHALL BE
 LIMITED TO WORK AREAS THAT INCLUDE EXITS OR CORRIDORS
 SHARED BY MORE THAN ONE TENANT WITHIN THE WORK AREA IN
 WHICH LEVEL 2 ALTERATIONS ARE BEING PREFORMED, AND
 WHERE SPECIFIED THEY SHALL APPLY THROUGHOUT THE FLOOR
 ON WHICH THE WORK AREAS ARE LOCATED OR OTHERWISE BEYOND
 THE WORK AREA.
  
 2A) WITH THIS BEING A LEVEL III ALTERATION THE EXTERIOR
 STAIRWAY BEING REPAIRED AND RELOCATED BASICALLY IN THE
 SAME LOCATION , PLEASE PROVIDE COMPLIANCE WITH 1022.5 .
 EXTERIOR EXIT STAIRWAYS SHALL BE LOCATED IN ACCORDANCE
 WITH SECTION 1023.3.
 1023.3 EXIT DISCHARGE LOCATION.
 EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE
 LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT
 LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS
 THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE
 PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE
 SEPARATION DISTANCE.
  
 2B) THE SECOND ISSUE WITH NOT KNOWING THE DISTANCE FROM
 THE PROPERTY LINE AT THE SECOND FLOOR DOOR OPENING IS
 IN TABLE 704.8 FOR UNPROTECTED OPENINGS 0-3-0? ZERO
 OPENINGS IN THE WALL LINE.
  
 2C) SHEET A-1.03 INDICATE A 5?X5? DOWNSPOUT, THE SITE
 PLAN INDICATES A 6?-0? HIGH SECURITY FENCE ALONG THE
 SAME PROPERTY LINE AND THE SURVEY INDICATES FROM THE
 BUILDING TO PROPERTY LINE A DISTANCE OF 2.90?. HOW WILL
 SECTION 1009.1EXCEPTION# 1 REQUIRING A 36? WIDE STAIR?
  
 2D) THE OTHER ISSUE IS WITH THE 5?X5? DOWNSPOUT, HOW
 WILL SECTION 1009.11.7 PROJECTIONS INTO THE REQUIRED
 WIDTH AT EACH HANDRAIL SHALL NOT EXCEED 4.5 INCHES AT
 OR BELOW THE HANDRAIL HEIGHT. NOTE HANDRAILS ARE TO BE
 CONTINUOUS SEE 1009.11.4 CONTINUITY.
  
 2E) THE PLANS FAIL TO INDICATE HANDRAILS AT EACH SIDE
 OF THE STAIRS. 1009.11.
  
 3) SHEET A-1.01 DOOR# 115-1 MACHINE ROOM, AGAIN THIS
 NEW ADDITION WALL LINES UP WITH THE EXISTING WALL THAT
 IS 2.90? FROM THE PROPERTY LINE. TABLE 704.8 THAT DOES
 NOT ALLOW OPENINGS UNTIL GRATER THAN 5.0? FROM THE
 PROPERTY LINE FOR UNPROTECTED OPENINGS. ALSO NOTE THIS
 DOOR NEEDS TO BE A 1-HR RATED DOOR AS TO 3006.4. THE
 ONE HR RATING WOULD ALLOW UNDER PROTECTED OPENINGS 15%
 ALLOWABLE OPENINGS AT DISTANCES OF 3?-0? AND GREATER.
 THE OTHER ISSUE IS THE DOOR SWING IS OVER THE ALLOWABLE
 EGRESS PATH. 1008.1.8.8.
  
 4) SHEET A-1.02 WINDOW OPENING 18A IS UNPROTECTED, IS
 AGAIN LESS THAN 5?-0? FROM THE PROPERTY LINE AND NOT
 ALLOWED TABLE 704.8.
  
 5) SHEET A-3.01 WEST ELEVATION INDICATES A LOUVERS ON
 THIS ELEVATION AGAIN UNPROTECTED OPENINGS WOULD NOT BE
 ALLOWED WITH UNPROTECTED OPENINGS, PLEASE SEE TABLE
 704.8 FOR UNPROTECTED OPENINGS AND FOR PROTECTED
 OPENINGS.
  
 6) THIS BUILDING DOES NOT PROVIDE ANY INFORMATION AS TO
 FIRE SPRINKLERS, SO IT IS ASSUMED TO BE AN
 UN-SPRINKLERED BUILDING. WITH THE R-2 OCCUPANCY AND THE
 ADDITION OF THE ELEVATOR THE REQUIREMENT FOR A AREA OF
 RESCUE ASSISTANCE NECESSARY. PLEASE REVIEW ALL THE
 REQUIREMENTS OF 11-4.3.11(1-3).
  
 6A) PLEASE INDICATE IF THE AREA OF RESCUE ASSISTANCE
 WILL BE LOCATED ON THE INTERIOR OF THE BUILDING OR IF
 IT WILL BE LOCATED ON THE EXTERIOR 2ND FLOOR LANDING OF
 THE BUILDING, AND NEEDING TO HAVE FIRE RATED WINDOWS
 AND DOORS. IN EITHER CASE PLEASE PROVIDE THE REQUIRED
 CLEAR FLOOR SPACE REQUIRED FOR THE AREA OF RESCUE
 ASSISTANCE AND THE MEANS OF EGRESS
  
 6B) PLEASE ALSO TAKE NOTE OF THE REQUIRED 48? CLEAR
 BETWEEN HANDRAILS,
 11-4.3.11.3.
  
 7) SHEET A-1.02 THE SECOND STORY LANDING INDICATES A
 SCUPPER LOCATED AT FLOOR LEVEL TO DRAIN WATER FROM THE
 LANDING. THE WATER THAT DRAINS FROM THE SCUPPER LANDS
 DIRECTLY ON TO THE STAIRS BELOW, PLEASE PROVIDE
 COMPLIANCE WITH 1009.5.2 OUTDOOR CONDITIONS.
  
 8) SHEET A-1.03 ROOF PLAN INDICATES ?GAF LIBERTY OR
 APPROVED EQUAL?, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 9) SHEET A-4.01 S-3.02 BOTH INDICATE A NEW SECOND STORY
 EPICORE CONCRETE PRE-ENGINEERED FLOOR SYSTEM, PLEASE
 PROVIDE ADDITIONAL INFORMATION ARE SHOP DRAWINGS BEING
 CREATED, INDICATING OF SPANS, LOADS TO BE IMPOSED,
 REINFORCING AND SHORING. 1905, 1907.
  
 10) PLEASE PROVIDE HOURLY RATING FOR THE EPICORE
 CONCRETE FLOOR SYSTEM, A 2HR FIRE RATING WILL BE
 REQUIRED BETWEEN THE R-2 OCCUPANCY AND BUSINESS
 OCCUPANCY BELOW. SEE TABLE 302.3.2& 712.4, ALSO PROVIDE
 FIRE RESISTANCE RATED ASSEMBLIES FOR THE PENETRATION OF
 THE SECOND STORY FLOOR ASSEMBLIES, 712.4.1.
  
 11) PLANS FAIL TO PROVIDE FLOOR/CEILING ASSEMBLIES
 SOUND RATING AS REQUIRED BY 1207.3. STRUCTURE-BORNE
 SOUND. FLOOR/ CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL
 HAVE AN IMPACT INSULATION CLASS RATING OF NOT LESS THAN
 50(45IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 12) SHEET A-1.02 WALL TYPE# 8 FAILS TO PROVIDE A STC
 RATING OF 50, 1207.2 AIR-BORNE SOUND.
  
 13) SHEET A-2.01 SECOND STORY CORRIDOR REFLECTED
 CEILING PLAN DOES NOT INDICATE THE EXIT SIGNS , 1006.3.
  
 14) PLANS S-1.01 INDICATE THE USE OF HELICAL PIER UNDER
 PINNING OF FOUNDATION, PLEASE PROVIDE SOILS REPORT .
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 15) SHEET S-0.01 IS USING THE WRONG VERSION OF THE
 ASCE-7-05.
 2004 FBC 1609.1.1 & CHAPTER 35 REFERENCED STANDARDS
 RECOGNIZES ASCE 7-02 . ALSO 1603.1.4 WIND DESIGN DATA.
  
 16) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:\
 16A) SINGLE HUNG WINDOWS
 16B) FIXED, STOREFRONT
 16C) MULLIONS
 16D) EXTERIOR GLAZED DOORS
 16E) EXTERIOR METAL DOORS
 16F) EXTERIOR LOUVER DOORS
 16G) WALL LOUVERS
 16H) LINTELS
 16I) ROOFING ASSEMBLIES, FLAT ROOF, UNDERLAYMENT?S,
 TILE AND ADHESIVES
  
 17) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 19) THE INPUT DATA REPORT FROM THE ENERGY CALCS DOES
 NOT MATCH THE PLANS, THE COUNT ON THE WINDOWS AND THE
 SQUARE FOOTAGE ARE OFF AND THE DOOR TYPE AND DOOR COUNT
 DOES NOT MATCH THAT OF THE PLANS. THERE ARE A TOTAL OF
 5 DOORS THAT LEAD INTO THE BUSINESS OFFICE PLEASE
 CORRECT. MISSING NORTH DOOR 101-2 AND PAIR OF DOORS
 102-1.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved