Plan Review Notes For Permit 08090239 |
Permit Number |
08090239 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-09-30 11:11:28 | ***DENIED*** | | | | 1) WORK SHALL COMPLY WITH NFPA 72, 2002 EDITION. | | SHEET-1, GENERAL NOTE #1 | | | | 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET-1, | | SEQUENCE OF OPERATIONS | | | | 3) PROVIDE AT LEAST (2) COPIES OF MANUFACTURER | | SPECIFICATION SHEETS FOR ALL EQUIPMENT TO BE INSTALLED. | | | | 4) ILLUSTRATE REQUIRED SMOKE DETECTOR ABOVE FACP ON | | DRAWINGS. | | | | 5) FIRE ALARM TO BE UL CERTIFICATED FOR CENTRAL STATION | | SERVICE. ADD NOTE TO PLANS | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|