Plan Review Notes
Plan Review Notes For Permit 08090239
Permit Number 08090239
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-30 11:11:28***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 72, 2002 EDITION.
 SHEET-1, GENERAL NOTE #1
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET-1,
 SEQUENCE OF OPERATIONS
  
 3) PROVIDE AT LEAST (2) COPIES OF MANUFACTURER
 SPECIFICATION SHEETS FOR ALL EQUIPMENT TO BE INSTALLED.
  
 4) ILLUSTRATE REQUIRED SMOKE DETECTOR ABOVE FACP ON
 DRAWINGS.
  
 5) FIRE ALARM TO BE UL CERTIFICATED FOR CENTRAL STATION
 SERVICE. ADD NOTE TO PLANS
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW