Plan Review Notes For Permit 08090201 |
Permit Number |
08090201 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-09-30 16:54:23 | REDLINED PLANS | | | | LOADS FOR DINING ROOM WERE NOT ADDED PER | | 210.52B1,210.11C1,220.52 AS NOTED ON PREVIOUS REVIEW. | | THIS ADDITIONAL LOAD OF 1500VA WILL NOT AFFECT THE | | SERVICE HOWEVER WILL NEED TO BE REVISED BEFORE FINAL. | | IF THERE ARE REVISIONS MADE BEFORE ROUGH, PLEASE REVISE | | AT THAT TIME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CONTACT. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVEIW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH |
|