2008-09-15 15:27:18PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. SHEET 1 OF 2, NOTES #12 INDICATES THAT THE KITCHEN
 CABINETS AND COUNTER TOPS ARE BEING REPLACED, HOWEVER
 THERE IS NO INDICATION OF THE SINK BEING REPLACED.
 PLEASE CLARIFY IF THE EXISTING SINK IS BEING REUSED OR
 IF A NEW ONE IS BEING INSTALLED.PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 3. SHEET 2 OF 3, SANITARY PLUMBING RISER: PLEASE
 CORRECT THE FOLLOWING PER THE FBC-2004 PLUMBING
 SECTIONS.
  
 A} THE SUBMITTED RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE 2ND FLOOR LAVATORY IS BEING INDICATED
 BETWEEN THE WATER CLOSET AND TUB, HOWEVER THE FLOOR
 PLAN IS INDICATING THE LAVATORY TO THE SIDE OF THE
 WATER CLOSET. AT A MINIMUM THE SANITARY RISER SHALL
 REFLECT THE PROPOSED FLOOR PLAN. PER SECTION 701.1
 SCOPE AND (W.P.B. AS AMENDED) SECTION 106.3.5.4(9)
 PLUMBING.
  
 B} A 3 INCH SOIL STACK IS REQUIRED FOR THE NEW PROPOSED
 2ND FLOOR PLAN PLUMBING. PER SECTION 701.1 SCOPE AND
 (W.P.B. AS AMENDED) SECTION 106.3.5.4(9) PLUMBING.
  
 C} A 3 INCH CLEAN OUT IS REQUIRED AT THE BASE OF THE
 SOIL STACK FOR THE 2ND FLOOR PLUMBING. PER SECTION
 708.3.4 BASE OF STACK.
  
 D} A VENT IS REQUIRED FOR THE 2ND FLOOR MASTER BATH
 TUB. PER A 1/4" = 1' SCALE THE TUB POINT OF VENT
 APPEARS TO BE ABOUT 9 FEET FROM TRAP. PER TABLE 906.1,
 A 2 INCH TRAP CAN ONLY BE 6 FEET FROM VENT.
  
 4. SHEET 2 OF 2, 2ND FLOOR DEMOLITION PLAN: CLEARLY
 INDICATE THE FOLLOWING ON THE DEMO PLAN PER FBC-2004
 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE REMOVAL OF
 ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND AN
 INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR TO
 COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR
 POURED CONCRETE SLABS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  