2008-09-15 15:27:18 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007 |
| REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5 |
| RETENTION OF CONSTRUCTION DOCUMENTS. |
| |
| 2. SHEET 1 OF 2, NOTES #12 INDICATES THAT THE KITCHEN |
| CABINETS AND COUNTER TOPS ARE BEING REPLACED, HOWEVER |
| THERE IS NO INDICATION OF THE SINK BEING REPLACED. |
| PLEASE CLARIFY IF THE EXISTING SINK IS BEING REUSED OR |
| IF A NEW ONE IS BEING INSTALLED.PER FBC-2004 PLUMBING |
| SECTION 401.1 SCOPE. |
| |
| 3. SHEET 2 OF 3, SANITARY PLUMBING RISER: PLEASE |
| CORRECT THE FOLLOWING PER THE FBC-2004 PLUMBING |
| SECTIONS. |
| |
| A} THE SUBMITTED RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. THE 2ND FLOOR LAVATORY IS BEING INDICATED |
| BETWEEN THE WATER CLOSET AND TUB, HOWEVER THE FLOOR |
| PLAN IS INDICATING THE LAVATORY TO THE SIDE OF THE |
| WATER CLOSET. AT A MINIMUM THE SANITARY RISER SHALL |
| REFLECT THE PROPOSED FLOOR PLAN. PER SECTION 701.1 |
| SCOPE AND (W.P.B. AS AMENDED) SECTION 106.3.5.4(9) |
| PLUMBING. |
| |
| B} A 3 INCH SOIL STACK IS REQUIRED FOR THE NEW PROPOSED |
| 2ND FLOOR PLAN PLUMBING. PER SECTION 701.1 SCOPE AND |
| (W.P.B. AS AMENDED) SECTION 106.3.5.4(9) PLUMBING. |
| |
| C} A 3 INCH CLEAN OUT IS REQUIRED AT THE BASE OF THE |
| SOIL STACK FOR THE 2ND FLOOR PLUMBING. PER SECTION |
| 708.3.4 BASE OF STACK. |
| |
| D} A VENT IS REQUIRED FOR THE 2ND FLOOR MASTER BATH |
| TUB. PER A 1/4" = 1' SCALE THE TUB POINT OF VENT |
| APPEARS TO BE ABOUT 9 FEET FROM TRAP. PER TABLE 906.1, |
| A 2 INCH TRAP CAN ONLY BE 6 FEET FROM VENT. |
| |
| 4. SHEET 2 OF 2, 2ND FLOOR DEMOLITION PLAN: CLEARLY |
| INDICATE THE FOLLOWING ON THE DEMO PLAN PER FBC-2004 |
| PLUMBING, SECTION 704.5 DEAD ENDS: IN THE REMOVAL OF |
| ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND AN |
| INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR TO |
| COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR |
| POURED CONCRETE SLABS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |