2008-09-11 14:25:31 | |
| |
| ** DENIED REVIEW ** |
| |
| |
| |
| 1) NOTE: PLEASE VERIFY SCOPE OF WORK AS PERMIT |
| APPLICATION STATES TO UPDATE ALL ELECTRICAL YET THE |
| PLANS INDICATE MUCH OF IT AS EXISTING? |
| FBC 106.1.1 FOR CLARITY OF SCOPE. |
| |
| IF APPLICATION STATES TO UPDATE ELECTRICAL HOW CAN THE |
| PLANS SHOW SEVERAL ROOMS WITH NO ELECTRICAL? |
| |
| 2) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AS THE |
| DINING ROOM RECEPTACLES SHALL NOT BE PART OF FAMILY |
| ROOM CIRCUIT AND SHALL MEET THE OTHER SECTIONS AS |
| NOTED. |
| PANEL SCHEDULE SHOWS 15AMP BREAKER AND #14 WHICH IS NOT |
| PERMITTED. |
| |
| 2) NOTE: PLEASE LIST ALL OF THE ARC FAULT PROTECTED |
| CIRCUITS ON PANEL SCHEDULE PER 210.12,408.4. |
| NONE LISTED AT THIS TIME. *** GFCI IS NOT THE SAME AS |
| AFCI*** |
| |
| 3) NOTE: PLEASE SEE 250.24, 250.6 AS NO EQUIPMENT |
| GROUNDING CONDUCTORS ARE PERMITTED BEFORE THE FIRST |
| MEANS OF DISCONNECT. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |