Plan Review Notes
Plan Review Notes For Permit 08090201
Permit Number 08090201
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-11 14:25:31 
  
 ** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE VERIFY SCOPE OF WORK AS PERMIT
 APPLICATION STATES TO UPDATE ALL ELECTRICAL YET THE
 PLANS INDICATE MUCH OF IT AS EXISTING?
 FBC 106.1.1 FOR CLARITY OF SCOPE.
  
 IF APPLICATION STATES TO UPDATE ELECTRICAL HOW CAN THE
 PLANS SHOW SEVERAL ROOMS WITH NO ELECTRICAL?
  
 2) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AS THE
 DINING ROOM RECEPTACLES SHALL NOT BE PART OF FAMILY
 ROOM CIRCUIT AND SHALL MEET THE OTHER SECTIONS AS
 NOTED.
 PANEL SCHEDULE SHOWS 15AMP BREAKER AND #14 WHICH IS NOT
 PERMITTED.
  
 2) NOTE: PLEASE LIST ALL OF THE ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE PER 210.12,408.4.
 NONE LISTED AT THIS TIME. *** GFCI IS NOT THE SAME AS
 AFCI***
  
 3) NOTE: PLEASE SEE 250.24, 250.6 AS NO EQUIPMENT
 GROUNDING CONDUCTORS ARE PERMITTED BEFORE THE FIRST
 MEANS OF DISCONNECT.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  