| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| ON ELECTRICAL PLANS AT A MINIMUM. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE SHOW GROUNDING LOCATION AND SYSTEM FOR |
| TRANSFORMER(S) PER 250.50,250.66,250.20,250.30. |
| |
| 3) NOTE: DISCONNECTS AT SHELTERS AND AT RESTROOM |
| BUILDING. RESTROOM BUILDING SHOWS A MAIN LUG ONLY |
| PANEL. PER 225.31-225.39 |
| |
| 4) NOTE: PLEASE SEE 250.32,250.50 FOR GROUNDING AT |
| SHELTERS AND AT RESTROOM BUILDING. |
| |
| 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| LEVELS/CALCULATIONS FOR LIGHTING PER FBC |
| 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3. |
| |
| 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR |
| WORST CASE FOR SERVICE FEEDERS AND BRANCH CIRCUITS PER |
| FBC 13-413.1.ABC.1.1, .1.2. |
| |
| 7) NOTE: PLEASE INDICATE WHERE CONTINUOUS LOADS ARE |
| FIGURED OR SHOWN. 215.3,230.42 ETC |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |