Plan Review Notes
Plan Review Notes For Permit 08090180
Permit Number 08090180
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-15 16:05:16 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PLANS SUBMITTED CONTAINED THE ELECTRICAL SHEET,
 LABELED #4, THAT WAS REVIEWED AND STAMPED PREVIOUSLY.
 SHEET #4 SUBMITTED AS NEW IS LABELED "NEW WALL SECTION"
 AND CONTAINS NO ELECTRICAL FLOOR PLAN. PER 106.1
 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL
 INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS WITH
 EACH APPLICATION FOR A PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  