2008-09-26 16:56:03 | 2004 FBC W/2007 REVISIONS |
| ENCLOSE CARPORT |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. FS 713 |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT 2 COPIES OF A SURVEY OR SITE PLAN SHOWING THE |
| DISTANCES FROM THE CARPORT WALLS TO THE PROPERTY LINES |
| AND STRUCTURES ON ADJACENT PROPERTY IF LESS THAN SIX |
| FEET TO PROPERTY LINES. FBC R302.1 AND R302.2 REQUIRES |
| EXTERIOR WALLS TO BE ONE HOUR FIRE RATED WITH NO |
| OPENINGS IF SEPARATED BY LESS THAN SIX FEET. |
| |
| 4) PLEASE LIST THE NAME AND CONTACT INFORMATION OF THE |
| PERSON RESPONSIBLE FOR THE DRAWINGS ON THE PLANS. |
| |
| 5) SUBMIT TWO COPIES OF COMPETED AND SIGNED ENERGY |
| CALCULATION FORMS ON THE PLANS. FBC 13-600 |
| |
| 6) SPECIFY THE WALL AND CEILING INSULATION ON THE |
| PLANS. FBC 13-600. |
| |
| 7) PROVIDE A WALL SECTION OF THE NEW WALL ON THE PLANS. |
| SPECIFY THE WALL FURRING, INSULATION, DRYWALL, EXTERIOR |
| FINISH, ETC. R301 |
| |
| 8) PROVIDE DOOR AND WINDOW BUCK DETAILS ON THE PLANS. |
| R613.6.1.1 |
| |
| 9) ON PAGE 3 OF THE PLANS THE C-2 COLUMNS ARE SPECIFIED |
| AS CAST IN PLACE CONCRETE, BUT APPEAR TO BE REINFORCED |
| FILLED CELL MASONRY. PLEASE CLARIFY. |
| |
| 10) ON PAGE 3 OF THE PLANS THE C-2 COLUMNS ARE |
| SPECIFIED AS 4'-8" O.C. AND NOTE #2 SPECIFIES |
| REINFORCING AT 48" (4') O.C. PLEASE CLARIFY. |
| |
| 11) THE C-1 COLUMNS ARE SPECIFIED AT 4'-8" O.C. BUT ARE |
| ONLY LOCATED WHERE THE NEW MASONRY WALLS ATTACH TO THE |
| EXISTING MASONRY WALLS. PLEASE CORRECT. |
| |
| 12) THE SIZE OF THE EXISTING FOOTINGS SUPPORTING THE |
| NEW MASONRY WALLS SHALL BE CAPABLE OF ACCOMMODATING ALL |
| LOADS AND TRANSMITTING THEM TO THE SOIL. FBC 403.1 |
| |
| 13) SPECIFY THE WINDOW AND DOOR SIZES AND TYPES ON THE |
| PLANS. R301.2(2) & FAC RULE 9B-72 |
| |
| 14) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL |
| EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE |
| FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM) |
| WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES |
| (152 MM) ELSEWHERE. |
| |
| 15) PAGE 2 OF THE PLANS SPECIFY IMPACT WINDOWS AND THE |
| PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| NON-IMPACT AND REQUIRE IMPACT PROTECTION. PLEASE |
| CORRECT. R301.2.1.2 |
| |
| 16) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR WINDOW |
| MULLIONS. FAC RULE 9B-72 |
| |
| 17) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| IN-SWING METAL DOOR. FAC RULE 9B-72 |
| |
| 18) SUBMIT 2 COPIES OF A KEY PLAN AND AN INSTALLATION |
| SCHEDULE FOR THE STORM PANELS REQUIRED BY FBC |
| R301.2.1.2, IF IMPACT RATED PRODUCTS ARE NOT TO BE |
| INSTALLED. |
| |
| 19) SPECIFY THE APPLICABLE CODE AND WIND DESIGN |
| INFORMATION ON THE PLANS. FBC R301 NOTE: THE CODE IS |
| THE FBC 2004 WITH 2007 REVISIONS AND THE WINDSPEED IS |
| 140 MPH (3 SECOND GUST) EXPOSURE CATEGORY B. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |