2008-09-26 15:43:18BUILDING PLAN REVIEW
 PERMIT: 08090174
 ADD: 2050N CONGRESS AVE
 CONT: ENGINEERED ENVIROMENTS INC
 TEL: (561)282-4111
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) COVER SHEET INDICATES THE WIND DESIGN TO ASCE 7-98,
 PLEASE CORRECT. 2004 FBC 1609.1.1 & CHAPTER 35
 REFERENECED STANDARDS RECOGNIZES ASCE 7-02 . ALSO
 1603.1.4 WIND DESIGN DATA.
  
 3) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4) PLANS INDICATE THE NEW ANTENNAS ARE BEING INSTALLED
 ON THE EXTERIOR OF THE VERTICAL EXIT ENCLOSURE. PLANS
 DO NOT INDICATE THE ROUTING OR INSTALLATION OF CABLES
 TO UNMANNED ATT CABINERTRY.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.