Plan Review Notes
Plan Review Notes For Permit 08090173
Permit Number 08090173
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-18 14:45:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. I AM IN RECEIPT OF THE LETTER INCLUDED IN THE PERMIT
 APPLICATION EXPLAINING THE SITUATION WITH BRITE LITE
 SHUTTERS. THE ORIGINAL PERMIT IS EXPIRED; THEREFORE,
 NEW PLANS AND A NEW PERMIT APPLICATION ARE REQUIRED
 (CANNOT DO A CHANGE OF CONTRACTOR). PLEASE INCLUDE ALL
 WORK (INCLUDING THE WORK COMPLETED BY THE FIRST
 CONTRACTOR) AS AN OPEN, ACTIVE PERMIT IS REQUIRED IN
 ORDER TO OBTAIN FINAL INSPECTION FOR THIS WORK. MY
 UNDERSTANDING IS THAT BUCHANAN SCREEN HAS BEEN HIRED TO
 RESOLVE OUTSTANDING ISSUES AS WELL AS INSTALL NEW
 HURRICANE SHUTTERS. IF THIS IS NOT CORRECT, AND
 BUCHANAN OBJECTS TO PERMITTING WORK WHICH THEY DID NOT
 INSTALL, PLEASE CONTACT ME IN ORDER TO DISCUSS OPTIONS
 TO GET THIS SITUATION RESOLVED.
  
 2. PLEASE REVISE THE INSTALLATION SCHEDULE AS FOLLOWS:
  
 A. THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH ANCHOR CHARTS; FOR INSTANT, WALL MOUNT
 A-A (AS SHOWN ON SHEET 3). ALL OF THE MOUNTING TYPES
 AND ALL SIX CHARTS WERE HIGHLIGHTED.
  
 B. PLEASE CLARIFY WHICH ANCHOR YOU ARE USING. THE
 INSTALLATION SCHEDULE STATES YOU ARE USING ITW, BUT
 BOTH ANCHORS A AND D ARE CIRCLED ON S;HEET 7. USE OF
 ANCHOR A, 1/4" TAPCONS, CONNECTION MOUNTING TYPE A-A,
 BLOCK SUBSTRATE, REQUIRES USE OF CHART 1 (SEE SHEET 3).
 THIS WOULD REQUIRE 6" ANCHOR SPACING, BUT THE
 INSTALLATION SCHEDULE SPECIFIES 9"/7". PLEASE REVISE.