Date |
Text |
2008-09-18 14:45:27 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. I AM IN RECEIPT OF THE LETTER INCLUDED IN THE PERMIT |
| APPLICATION EXPLAINING THE SITUATION WITH BRITE LITE |
| SHUTTERS. THE ORIGINAL PERMIT IS EXPIRED; THEREFORE, |
| NEW PLANS AND A NEW PERMIT APPLICATION ARE REQUIRED |
| (CANNOT DO A CHANGE OF CONTRACTOR). PLEASE INCLUDE ALL |
| WORK (INCLUDING THE WORK COMPLETED BY THE FIRST |
| CONTRACTOR) AS AN OPEN, ACTIVE PERMIT IS REQUIRED IN |
| ORDER TO OBTAIN FINAL INSPECTION FOR THIS WORK. MY |
| UNDERSTANDING IS THAT BUCHANAN SCREEN HAS BEEN HIRED TO |
| RESOLVE OUTSTANDING ISSUES AS WELL AS INSTALL NEW |
| HURRICANE SHUTTERS. IF THIS IS NOT CORRECT, AND |
| BUCHANAN OBJECTS TO PERMITTING WORK WHICH THEY DID NOT |
| INSTALL, PLEASE CONTACT ME IN ORDER TO DISCUSS OPTIONS |
| TO GET THIS SITUATION RESOLVED. |
| |
| 2. PLEASE REVISE THE INSTALLATION SCHEDULE AS FOLLOWS: |
| |
| A. THE SHUTTER CONNECTION MOUNTING TYPE SHOULD |
| CORRELATE WITH ANCHOR CHARTS; FOR INSTANT, WALL MOUNT |
| A-A (AS SHOWN ON SHEET 3). ALL OF THE MOUNTING TYPES |
| AND ALL SIX CHARTS WERE HIGHLIGHTED. |
| |
| B. PLEASE CLARIFY WHICH ANCHOR YOU ARE USING. THE |
| INSTALLATION SCHEDULE STATES YOU ARE USING ITW, BUT |
| BOTH ANCHORS A AND D ARE CIRCLED ON S;HEET 7. USE OF |
| ANCHOR A, 1/4" TAPCONS, CONNECTION MOUNTING TYPE A-A, |
| BLOCK SUBSTRATE, REQUIRES USE OF CHART 1 (SEE SHEET 3). |
| THIS WOULD REQUIRE 6" ANCHOR SPACING, BUT THE |
| INSTALLATION SCHEDULE SPECIFIES 9"/7". PLEASE REVISE. |