2009-01-13 10:20:59 | ELECTRICAL POLE BUILDING REVIEW THIRD CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- PERMIT APPLICATION IS FOR THE LIFT STATION |
| ELECTRICAL WORK ONLY. A SEPARATE PERMIT APPLICATION IS |
| REQUIRED FOR THE LIFT STATION. THE FOLLOWING COMMENTS |
| APPLY ONLY TO THE ELECTRICAL WORK ON PERMIT APPLICATION |
| SUBMITTED. |
| |
| 2- LIGHT POLE ENGINEERED CALCULATIONS SUBMITTED: |
| A) "ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, |
| ADDRESS AND NUMBER ON EACH SHEET" AS REQUIRED BY SEC. |
| 61G15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE AND |
| CHAPTER 471 FLORIDA STATUTE. |
| |
| B) NEED TO PROVIDE THE ENGINEERING FIRM "PRINCIPAL |
| ENGINEERING" CERTIFICATE OF AUTHORIZATION NUMBER AS |
| REQUIRED BY SEC. 61G15-23.002(2) OF FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| |
| C) ALL SHEETS NEED TO BE SIGNED AND SEALED WITH |
| ORIGINAL SEAL AND SIGNATURE, NOT COPY OF THE SIGNATURE. |
| SEE FLORIDA ADMINISTRATIVE CODE SECTION AND FLORIDA |
| STATUTE SECTION CITED ABOVE. CALCULATIONS SUBMITTED ARE |
| SEALED ONLY ON THE FRONT PAGE AND THE SIGNATURE IS A |
| PHOTOCOPY. RESUBMIT CALCULATIONS COMPLYING WITH ALL THE |
| ADMINISTRATIVE CODE AND FLORIDA STATUTE REQUIREMENTS. |
| |
| 3- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED |
| CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED |
| CALCULATIONS REQUIRED ON ITEM #1 ABOVE. ENGINEER TO |
| REVIEW THOSE SHOP DRAWINGS PRIOR TO SUBMITTAL TO THIS |
| OFFICE. |
| |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL |
| ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS |
| AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |