Plan Review Notes For Permit 08090166 |
Permit Number |
08090166 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-11-06 11:39:04 | ELECTRICAL POLE BUILDING REVIEW SECOND CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | ***NOTE: NONE OF THE COMMENTS FROM FIRST CHECKLIST WERE | | ADDRESSED. SEE COMMENTS BELOW: | | | | 1- PROVIDE THE LIGHT POLE ENGINEERED CALCULATIONS AS | | REQUIRED BY NOTE ON LIGHT POLE DETAIL AND BY SEC. 1609 | | OF FBC 2004. | | | | 2- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED | | CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED | | CALCULATIONS REQUIRED ON ITEM #1 ABOVE. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL | | ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS | | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|