2008-09-25 17:05:21 | ADDITION BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT |
| PICK UP. |
| |
| 2- FLAT ROOF PRODUCT APPROVAL: SELECTED ASSEMBLY ON |
| PAGE 17 AND 18 OF NOA 06-0626.04 SUBMITTED IS LIMITED |
| BY GENERAL LIMITATION #9 AND IS GOOD ONLY FOR -45PSF |
| MAXIMUM DESIGN PRESSURE. ACCORDING TO GENERAL |
| LIMITATION #9 (SEE LAST PAGE OF NOA) NAIL ENHANCING FOR |
| PERIMETER AND CORNER AREAS IS NOT ALLOWED. NEED TO |
| SELECT ANOTHER APPROVED ASSEMBLY THAT ALLOWS NAIL |
| ENHANCING AT PERIMETER AND CORNER AREAS TO MEET THE |
| UPLIFT LOADS REQUIRED BY TABLE 1609.6.2.1(2) OF 2004 |
| FBC. TYPICALLY APPROVED ASSEMBLIES THAT ARE LIMITED BY |
| GENERAL LIMITATION #7 ALLOWS NAIL ENHANCING BY |
| PROVIDING RAS 117 CALCULATIONS. SEE GENERAL LIMITATION |
| #7 ON SHEET 24 OF NOA SUBMITTED. |
| NOTE: RAS 117 CALCULATIONS NEED TO BE SIGNED ADN SEALED |
| BY ANY OF THE PROFESSIONALS LISTED ON GENERAL |
| LIMITATION #7. |
| |
| 3- DIMENSIONS SHOWN ON ARCHITECTURAL PLANS DON'T MATCH |
| DIMENSIONS SHOWN ON SURVEY. ALSO, SURVEY DOESN'T SHOW |
| ANY EXISTING STAIRS AT REAR OF BUILDING. REVISE/CLARIFY |
| AS NECESSARY TO MATCH. |
| |
| 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| IS TOO LOW. NEED TO UPDATE VALUATION TO INCLUDE ALL |
| DESIGNER FEES AND CONTRACTOR'S FEES AS REQUIRED BY SEC. |
| 108.3 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS AND DETAILS. |
| ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SELECTED CONNECTOR |
| ONLY. |
| |
| 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 7- PLANS NEED TO SPECIFY ROOF SLOPE TO VERIFY |
| COMPLIANCE WITH SEC. 1507.11.1 OF 2004 FBC. |
| |
| 8- SPECIFY HOW LONG ARE THE ANCHOR BOLTS USED TO FASTEN |
| THE STEEL COLUMNS BOTTOM PLATE. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE |
| UPLIFT LOADS OF SEC. 1609 OF 2004 FBC. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561) 805-6712 |