Plan Review Notes
Plan Review Notes For Permit 08090142
Permit Number 08090142
Review Stop E
Sequence Number 3
Notes
Date Text
2009-04-08 12:36:23** PROVISO**
 BEFORE ROUGH ELECTRICAL INSPECTIONS.
  
 1) NOTE: ALL ELECTRICAL IN ROOMS, 1.00, 101 AND 1.02 TO
 BE COMPLETED AND REVISED TO CIRCUIT AND SHOW ALL
 ELECTRICAL FROM TENANT SPACE ELECTRICAL SERVICE.
 THIS WAS CONFIRMED WITH ELECTRICAL ENGINEER AS WELL AS
 GC AND EC.
 310.16, 240.4, 408.4 ETC
  
 **REDLINED
 LOW VOLTAGE FOR FIRE ALARM, DATA SYSTEMS EACH UNDER
 SEPARATE PERMITS.
 SERVICE ENTRANCE CONDUCTORS ENCASED IN CONCRETE PER
 230.6.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  