2009-02-25 09:40:55 | ** NOTE: ONE SET OF ELECTRICAL PLANS HAVE BEEN REMOVED |
| FROM SETS AND WILL BE RETAINED BY THIS OFFICE. |
2009-02-25 09:38:19 | ** DENIED 2ND REVIEW ** |
| |
| 1ST REVIEW UNDER PERMIT APPLICATION. |
| 2ND REVIEW. |
| |
| |
| |
| 1) NOTE: PLEASE BE SURE TO ADJUST CODES AND DESIGNS FOR |
| THE FOLLOWING. THE PERMIT APPLICATION HAS ONLY NOW BEEN |
| MADE. PER FAC 69A-60.004 AND .003 NFPA-1 AND NFPA-101 |
| HAS BEEN REVISED TO THE 2006 EDITIONS OF EACH. |
| THIS IS A SEPARATE ADOPTED RULING FROM THE STATE AND IS |
| NOT BASED ON THE NEW CODE ADOPTIONS OF MARCH 1ST 2009. |
| PLEASE REVISE ANY NEEDED DESIGNS AND REVISED CODE |
| REFERENCES ON PLANS. |
| |
| 2) NOTE: AS STATED ON PREVIOUS REVIEWS. THE BASE |
| BUILDING DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY. |
| ALL PLANS SHALL GO BACK TO THE BASE BUILDING DESIGNERS |
| OF RECORD FOR *SHOP DRAWING REVIEW STAMP* AND SIGNATURE |
| FROM EACH INDIVIDUAL DESIGNER OF RECORD. |
| THIS BUILDING IS UNDER THE RESPONSIBILITY OF EACH OF |
| THOSE DESIGNERS UNTIL SUCH TIME THE BUILDING IS |
| COMPLETE BASED ON PERMITTED SCOPE OF WORK ON PLANS FOR |
| C OF O, C OF C, ETC. |
| FS 471,481 |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS. NO NEW |
| SERVICE WITH SEPARATE METER WILL BE GRANTED. IN SEVERAL |
| MEETINGS HELD BEFORE PLANS WERE RESUBMITTED THE REQUEST |
| WAS MADE FOR THE SEPARATE MAIN IN ORDER FOR ALL |
| ELECTRICAL IN THE TENANT SPACE TO BE FED SEPARATELY SO |
| THAT THE TENANT COULD BE METERED SEPARATELY FROM FPL |
| AND PAY THEIR OWN ELECTRIC BILL. |
| IN THE MEETINGS HELD IT WAS AGREED TO REMOVE COMMON |
| AREAS WHICH WERE BEING FED FROM TENANT MAIN AND TO HAVE |
| ACTUAL TENANT SEPARATION. |
| THIS WAS ALSO BASED ON THE EGRESS LIGHTING IN TENANT |
| SPACE BEING FED FROM BATTERY BACK UP FIXTURES IN ORDER |
| TO EXIT OCCUPANTS FROM THE BUILDING IN THE EVENT OF |
| POWER FAILURE/EMERGENCY. |
| THE PLANS HAVE NOW BEEN COMPLETELY REVISED TO SHOW A |
| SUBSTANTIAL AMOUNT OF *GENERAL LIGHTING* WHICH HAPPENS |
| TO BE BATTERY BACK UP FIXTURES ALSO BEING FED FROM THE |
| CITY'S ELECTRICAL SERVICE MAIN WHICH IS PART OF THE |
| CITY'S METERING AND BILLING. THIS IS NOT WHAT WAS GONE |
| OVER IN THE MEETINGS AND MANY DISCUSSIONS. THIS IS |
| COMPLETELY OPPOSITE FROM THE REASON A SEPARATE |
| SERVICE/MAIN WAS REQUESTED IN ORDER TO METER SEPARATELY |
| FOR TENANT. ESSENTIALLY BASED ON THE ELECTRICAL SHOWN |
| MUCH OF THE ELECTRICAL LIGHTING IS FED FROM THE CITY'S |
| ELECTRICAL SERVICE WHICH WOULD NOW AFFECT THE 700 AND |
| 701 SYSTEMS FOR SELECTIVE COORDINATION. |
| THE TENANT BATH ROOMS AND OTHER AREAS ARE ALSO STILL |
| BEING SHOWN BEING FED FROM THE BASE BUILDING'S |
| ELECTRICAL SYSTEM. THIS BATHROOM IS LOCATED IN THE |
| TENANT SPACE ALONG WITH SHIPPING AND RECEIVING. THIS |
| WOULD ELECTRICAL SYSTEMS CROSSED INTO THE TENANT SPACE. |
| THIS WILL ALSO NOT BE PERMITTED. |
| THE TENANT MAY GO BACK TO THE BASE BUILDING ELECTRICAL |
| SERVICE AS THERE IS SPACE, LOAD AND DESIGN FOR THE |
| TENANT. |
| 230.2, 700.27, 700.18, 700.12F, 240.12 ETC. |
| |
| 4) NOTE: AS NOTED ON PREVIOUS REVIEW. PLEASE SUBMIT |
| COMPLETE LIGHTING PERFORMANCE CALCULATIONS BASED ON |
| 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| PLEASE SEE SECTION AS NOTED FOR TRACK LIGHTING. THE |
| WATTAGE MUST BE BASED ON THE RATING OF THE FIXTURE |
| TIMES THE NUMBER OF FIXTURES, OR 30WATTS PER FOOT WHICH |
| EVER IS GREATER. |
| |
| AN EXAMPLE: THE WATTAGE PER SQ FT SHOWN FOR MUSEUM AREA |
| IS 1.7. THE CODE IN TABLE *B* ALLOWS 1.0 AND THEN ONLY |
| THE ADDITIONAL FOR THE ACTUAL DISPLAY OR ACCENT |
| LIGHTING IS EXEMPT. THIS IS NOT AN AREA FOR RESTORATION |
| WORK WHICH IS WHAT SEEMS TO BE THE ALLOWANCE SHOWN. |
| |
| THE WATTAGE MUST BE BASED ON FIXTURE/BALLAST VA. SEE |
| FIXTURES A AND B FOR EXAMPLE. IN THE CALCULATIONS THE |
| COMPLETE FIXTURE WATTAGE IS SHOWN AT 30WATTS. HOW IS |
| THIS POSSIBLE WHEN EACH OF THESE FIXTURES CONTAIN |
| 2-32WATT BULBS BASED ON THE FIXTURE LEGEND? EVEN WITH |
| SOME OF THE MOST EFFICIENT BALLAST AVAILABLE ON THE |
| MARKETS, THE WATTAGE WOULD NOT BE CUT INTO LESS THAN |
| HALF. BASE ON THE CALCULATIONS AND DERIVED WATTAGE |
| THERE SEEMS TO BE SOME SORT OF MISPRINT OF ACTUAL |
| FIXTURE WATTAGE. |
| |
| ANOTHER EXAMPLE WOULD BE SPACE 1.14 WHICH SHOWS A |
| FIXTURE WATTAGE FIGURED INTO THE CALCULATIONS OF 30 |
| WATTS HOWEVER BASED ON THE MAXIMUM WATTAGE PER FIXTURE |
| AS STATED ON THE FIXTURE LEGEND THE FIXTURES WOULD BE A |
| MAXIMUM OF 37WATTS. THIS WOULD BE THE WATTAGE NEEDED TO |
| BE FIGURED INTO THE CALCULATIONS. THIS IS ONLY THE |
| WATTAGE *IF* THE TOTAL WATTAGE OF FIXTURES TIMES THE |
| NUMBER OF FIXTURES IS LOWER THAN THE 30VA PER FT OF |
| TRACK ON PLANS. (AS NOTED ABOVE). |
| |
| THERE ARE OTHER AREAS AND ROOMS SUCH AS COMPUTER LAB |
| WHICH SHOWS A *0* WATTAGE IN DESIGN. THESE CALCULATIONS |
| MUST BE BASED ON SPACE BY SPACE. HOW CAN THESE VALUES |
| BE *0*? |
| PLEASE SEE CODE SECTIONS AS NOTED ABOVE. |
| THESE ARE ONLY SOME EXAMPLES AS IS NOT A LIST OF EACH |
| ITEM NOT SHOWN FOR CODE COMPLIANCE AND COORDINATION. |
| FBC 106.1.1,106.1.2, CLARITY AND COORDINATION. |
| |
| 5) NOTE: THERE SHALL BE NO STORAGE IN ELECTRICAL ROOMS |
| WHICH CONTAIN ELECTRICAL PANELS, TRANSFORMERS AND OVER |
| CURRENT PROTECTION. PLANS INDICATE COMPUTER STORAGE |
| WHICH IS NOT PERMITTED IN ROOM 2.13. |
| 408.17, 240.24, 110.26. |
| SHALL ALSO CONTAIN SIGNAGE: ELECTRICAL ROOM, NO STORAGE |
| PER FIRE MARSHAL OR WORDS TO THAT AFFECT. |
| |
| 6) NOTE: PLEASE SEE NEW WATER HEATER SHOWN UNDER |
| COUNTER DOES NOT CONTAIN ANY CIRCUITING OR DISCONNECT. |
| PLEASE COMPLETE SO THAT LOADS, CIRCUITING ETC MAY BE |
| REVIEWED. |
| 4220.30,4220.31,408.4, 310.16 |
| FBC 106.1, 106.1.2 FOR CLARITY, ADDITIONAL INFORMATION. |
| |
| 7) NOTE: PLEASE SEE SHEET E1.03 WHICH REFERENCES THE |
| 2007 FBC FOR ADA COMPLIANCE. THIS PROJECT HAS BEEN |
| APPLIED FOR PERMIT UNDER THE 2004 FBC W/2007 REVISION. |
| PLEASE REVISE. |
| |
| *** IT IS IMPORTANT TO KNOW AS THERE WILL BE |
| SUBSTANTIAL CHANGES TO PLANS THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT |
| THIS TIME. |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |