2008-09-10 11:30:29 | PLAN REVIEW DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SINCE THE SHELL BUILDING HAS NOT BEEN COMPLETED, AND |
| NO CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED, BUT DESIGN |
| TEAM OF THE SHELL BUILDING SHALL REVIEW THE PLANS FOR |
| THE BUILD-OUT AND IF APPROVED, SHALL THEN STAMP THE |
| PLANS AS REVIEWED AND ACCEPTED WITH A SHOP DRAWING |
| STAMP OF APPROVAL. |
| |
| 2. THE ADDRESS AND SPACE NUMBER SHALL BE INDICATED IN |
| THE TITLE BLOCK OF EACH SHEET. SECTION 106.1.1. |
| |
| 3. SHT A0.00 CODES & STANDARDS SHALL READ 2004 BUILDING |
| CODE WITH 2005, 2006 & 2007 REVISIONS. SECTION 106.1.2. |
| |
| 4. SHT A0.01 OCCUPANCY & EGRESS ANALYSIS INDICATES |
| ASSEMBLY OCCUPANCY - UNCONSENTRATED NET SF 15. PER |
| TABLE 1004.1.2 IT CALLS FOR TABLES & CHAIRS. PLEASE |
| SHOW THE TABLES & CHAIRS ON THE FLOOR PLAN FOR THE |
| ASSEMBLY OCCUPANCY. |
| |
| 5. SHT A0.02 LOUNGE ROOM 2.24 DOES NOT REFLECT |
| INFORMATION SHOWN ON SHT P2.1. A SINK IS SHOWN ON THE |
| PLUMBING SHEET BUT NOT ON THE ARCHITECTURAL SHEET. |
| PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 6. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING |
| COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS. |
| SHOW THE CLEAR FLOOR SPACE ON THE FLOOR PLAN. CABINET |
| DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| |
| 7. SHT P2.1 A WATER HAMMER ARRESTOR IS REQUIRED ON THE |
| WATER SUPPLY LINE TO THE REF. SECTION 604.9. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |