2008-09-16 11:28:30 | REVIEW #: 1ST **PLAN CHECK ONLY** |
| ACTION: |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THIS PLAN IS BEING SUBMITTED FOR PLAN REVIEW ONLY AT |
| THIS TIME. IF A PERMIT APPLICATION IS SUBMITTED PRIOR |
| TO COMPLETION OF THE BASE BUILDING, THESE TENANT PLANS |
| WILL NEED TO BE REVIEWED BY THE BASE BUILDING DESIGN |
| TEAM FOR APPROVAL PRIOR TO SUBMISSION. |
| |
| 1. PAGE M2.1: THE GROUP BATHROOMS ON THIS PAGE APPEAR |
| AS THOUGH THEY ARE INTENDED TO BE A PART OF THIS TENANT |
| SPACE RATHER THAN A PART OF THE BASE BUILDING. THIS AND |
| OTHER AREAS DO NOT SHOW ANY PROVISIONS FOR TENANT |
| SEPARATION. ALSO, THE EXISTING DUCTWORK SHOWN IN THIS |
| AREA DOES NOT MATCH THAT SHOWN ON THE CURRENT PERMIT |
| BASE BUILDING PLANS. PLEASE COORDINATE WITH THE BASE |
| BUILDING DESIGN TEAM AND CONTRACTOR TO CLEARLY SHOW |
| AREAS OF TENANT SEPARATION AND PROTECTION OF |
| PENETRATIONS IN ACCORDANCE WITH FBCM 607.5 AND FBCM |
| 607.8. |
| |
| 2. PAGE M4.1: THERE IS A NOTE INDICATING OUTSIDE AIR |
| AND EXHAUST AIR ARE EXISTING AND NO CHANGES ARE NEEDED. |
| HOWEVER, THE OCCUPANCY CLASSIFICATION AND OCCUPANT |
| LOADS FOR VENTILATION PURPOSES WERE NOT KNOWN UNTIL |
| THIS PHASE OF THE DESIGN. THEREFORE, PLEASE PROVIDE |
| VENTILATION CALCULATIONS WHICH INCLUDE OCCUPANCY |
| CLASSIFICATION, OCCUPANT LOADS, REQUIRED OUTSIDE AIR |
| AND THE OUTSIDE AIR PROVIDED IN ACCORDANCE WITH FBCM |
| TABLE 403.3. |
| |
| 3. PAGE M5.1: DETAIL 1 IS FOR FIRE DAMPER INSTALLATION. |
| THIS DETAIL IS NOT LIKELY TO CORRESPOND WITH THE FIRE |
| DAMPER MANUFACTURER?S INSTALLATION INSTRUCTIONS. FIRE |
| DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS SHALL |
| BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS AND LISTING PER FBCM 607.2. |
| PLEASE COORDINATE THIS DETAIL WITH THE MANUFACTURER?S |
| INSTRUCTIONS OR AT A MINIMUM, PROVIDE A NOTE WHICH |
| DEFERS TO THE MANUFACTURER?S INSTRUCTIONS TO |
| DEMONSTRATE COMPLIANCE WITH THIS SECTION. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| RONALD J. REGUEIRO |
| 561.805.6719 |
| [email protected] |