Plan Review Notes For Permit 08090142 |
Permit Number |
08090142 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-09 10:48:40 | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 2. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE | | DAILY. | | | | 3. SOME EXIT SIGNS APPEAR TO BE MISSING FROM WITHIN | | STAIR # 10 ALONG THE PATH OF THE EXIT ARROW. | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | SPRINKLER SYSTEM REMODEL. | | | | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | ALARM SYSTEM REMODEL. | | | | 6. PLEASE DISPLAY ALL RATED FIRE WALLS IN AND AROUND | | THE PROPOSED PHOTOGRAPHIC CENTRE. | | | | 7. PLEASE CLEARLY DELINEATE ALL EMERGENCY LIGHTING | | EQUIPMENT CONTAINED WITHIN THE PROPOSED SPACE. | | | | 8. NO DOOR SCHEDULE PROVIDED. A DOOR SCHEDULE SHALL | | INDICATE RATING, SIZE AND APPROPRIATE HARDWARE BEING | | PROPOSED FOR THE SPACE. | | | | 9. ON PAGE A).00 PLANS INDICATE THAT INTERIOR FINISHES | | SHALL COMPLY WITH FBC 803. PLEASE INDICATE SPECIFIC | | RATINGS FOR WALLS AND CEILINGS ON THE PLANS. | | | | 10. EXITS NOT PROPERLY SEPARATED IN EXHIBITION SPACE | | 1.12,1.13,OR 1.14 AREA. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | | | |
|