2008-09-30 09:48:20 | |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY |
| AND NOT FOR PERMITTING. PLEASE KNOW EVEN ONCE PLANS ARE |
| FOUND TO BE CODE COMPLIANT FOR ISSUANCE IF PERMIT |
| APPLICATION HAS NOT BEEN MADE PLANS WILL REMAIN IN A |
| FAILED STATUS. |
| |
| 2) NOTE: THE BASE BUILDING DOES NOT CONTAIN A |
| CERTIFICATE OF OCCUPANCY AT THIS TIME. THE BASE |
| BUILDING IS STILL UNDER THE RESPONSIBILITY OF THE BASE |
| BUILDING DESIGN TEAMS FOR ALL TRADES. IF THIS SCOPE OF |
| WORK IS PERMITTED BEFORE THE CO OF THE BASE BUILDING, |
| ALL PLANS AND DOCUMENTS ARE REQUIRED TO BE REVIEWED AND |
| *SHOP DRAWING* REVIEW STAMPED AND SIGNED BY EACH |
| DESIGNER OF RECORD FOR THE BASE BUILDING. |
| |
| 3) NOTE: PLEASE SEE THE NEW PROPOSED SERVICE SHOWN ON |
| PLANS IS NOT GRANTED PER 230.2. THE BASE BUILDING HAS |
| ALLOWANCE IN EXISTING EQUIPMENT FOR THIS SPACE FOR |
| FUTURE TENANT. A NEW SERVICE AS SHOWN DOES NOT MEET ANY |
| ALLOWANCES TO GRANT AN ADDITIONAL SERVICE TO THIS |
| SPACE. THIS HAS BEEN CONFIRMED WITH THE CHIEF |
| ELECTRICAL INSPECTOR |
| AS SHOWN THIS TENANT SPACE WOULD ALSO HAVE ELECTRICAL |
| LIGHTING BEING FED FROM BASE BUILDING ELECTRICAL |
| SYSTEMS FOR EMERGENCY LIGHTING ETC FROM ANOTHER |
| SERVICE. |
| |
| 4) NOTE: LOCATION OF ALL PROPOSED ELECTRICAL EQUIPMENT |
| IS NOT CLEAR AT THIS TIME. PLANS SEEM TO INDICATE SOME |
| ELECTRICAL EQUIPMENT IN THE BASE BUILDING AND NOT IN |
| THE TENANT SPACE OR ELECTRICAL ROOM. THE EQUIPMENT ON |
| MEZZANINE LEVEL IS IN THE CITY SPACE/EQUIPMENT ROOM |
| WHICH WILL NOT BE PERMITTED. COMMON AREA CORRIDORS, |
| ACCESS ETC ALL NEEDS TO BE CONFIRMED. |
| 110.26, 240.24 |
| FBC 106.1.1, FOR CLARITY AND ADDITIONAL INFORMATION |
| NEEDED. |
| |
| 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR TENANT |
| SPACE. LOADS AT THIS TIME ARE ALL SHOWN AT CONNECTED |
| LOADS. HOW IS TRACK LIGHTING LOADS FIGURED? HOW ARE |
| CONTINUOUS LOADS FIGURED? ARE ALL THESE ALREADY FIGURED |
| INTO LOADS AS SHOWN? |
| IF THIS IS THE CASE PLEASE SHOW AND INDICATE. |
| PLEASE SHOW LOADS ON THE EXISTING SERVICE WHICH THIS |
| TENANT SPACE WILL BE FED FROM. |
| NEC 220.87, 220.43B, 220.43A, 215.3, 230.42 ETC |
| FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| CLARITY. |
| |
| 6) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS. AS NO LPC |
| WERE SUBMITTED A REVIEW FOR THESE SECTIONS OF THE |
| FLORIDA BUILDING CODE COULD NOT BE DONE. PLEASE BE SURE |
| TO SEE THE SECTIONS NOTED ABOVE SPECIFIC TO TRACK |
| LIGHTING. |
| PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND WITH |
| SPECIFIC FIXTURES. AN EXAMPLE OF THE FIXTURES NOT |
| SHOWING INFORMATION WOULD BE THE XENON STRIP LIGHTING. |
| |
| 7) NOTE: PLEASE ADJUST CODES NOTED. SHOULD READ THE |
| 2004 FBC W/2007 REVISIONS. |
| |
| 8) NOTE: PLEASE BE SURE TO SHOW CONNECTIONS OF ANY |
| TRANSFORMERS PER 250.53,250.58,250.66. THERE IS A |
| GROUNDING ELECTRODE RISER IN THE EXISTING BUILDING |
| WHICH REQUIRES ANY TRANSFORMER TO BE CONNECTED TO. AS |
| THE LOCATIONS PROPOSED FOR ELECTRICAL EQUIPMENT IS NOT |
| GRANTED OR KNOWN TO BE FINAL AT THIS TIME, THE LOCATION |
| OF EQUIPMENT IN THE PROXIMITY OF THE EXISTING RISER MAY |
| HELP. |
| |
| 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. PLEASE |
| INDICATE HEIGHTS, LOCATIONS, AND LEVELS FOR ALL DEVICES |
| FOR ADA COMPLIANCE. |
| |
| 10) NOTE: AS A NOTE: THE NEW SERVICE AS SHOWN IS NOT |
| GRANTED, HOWEVER 230.6 DOES NOT PERMIT A FOUR HR |
| ENCLOSURE. THE CODE WOULD REQUIRE ENCASEMENT OF |
| CONCRETE OF A MINIMUM OF 2 INCHES. 230.70 |
| |
| 11) NOTE: PLANS ARE SHOWING COMMON AREA SPACES BEING |
| FED FROM THIS TENANT SPACE EQUIPMENT. AN EXAMPLE OF |
| THIS WOULD BE THE OUTSIDE THE BATHROOMS. SEPARATION OF |
| TENANT SPACES DEFINED AREAS ETC WILL ALL NEED TO BE |
| SPECIFIC. |
| AS THERE ARE MANY UNANSWERED QUESTIONS ON SEPARATION AT |
| THIS TIME AND SOME INFORMATION NOT YET SUBMITTED, THERE |
| MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| 12) NOTE: PROJECT WILL REQUIRE ADDRESSING FOR NEW |
| SPACE. PLEASE CONTACT JAMES JUDGE FOR |
| ADDRESSING.(561-822-1226) THE PLANS NEED TO SHOW THE |
| MAIN ADDRESS OF 401 CLEMATIS ON ALL TITLE BLOCKS |
| INCLUSIVE OF ALL TRADES. THE SUITE/UNIT NUMBER WILL BE |
| SEPARATELY ASSIGNED. |
| FAC 61G1-16.004, 61G15-23.002 |
| FBC 106.5 |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |