2008-09-24 14:53:42 | BUILDING PLAN REVIEW |
| PERMIT: 08090142 (PLAN REVIEW) |
| ADD: 401 CLEMATIS ST. SUITE # . |
| CONT: (PLAN REVIEW) CONTACT: TED DAVIS |
| TEL: (561)###-#### |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS.THE COVER SHEEET |
| NEGLECTS THE 2007 SUPPLEMENTS TO THE 2004 FBC, PLEASE |
| CORRECT. 106.1.2 ADDITIONAL INFORMATION REQUIRED, |
| 553.73FL S S . |
| |
| 1D) THIS TENANT SPACE IS LEASEABLE SPACE AND WILL |
| REQUIRE A SUITE ADDRESS, TO BE PROVIDED BY ADDRESS |
| TECHNITION JAMES JUDGE, AND WILL NEED TO BE ON THE |
| PERMIT APPLICATIONAS WELL AS PLANS. |
| |
| 2) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED |
| THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING |
| DESIGNER WILL NEED TO REVIEW THE SUBMITTED PLANS AND |
| AFFIX THEIR SHOP DRAWING STAMP ON THE PLANS. THE PLANS |
| SUBMITTED MAY EFFECT THEIR ENERGY CALCULATION |
| ASSUMPTIONS. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 3) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED |
| THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING |
| CONTRACTOR SHALL PROVIDE A NOTIRIZED LETTER INDICATING |
| ALLOWING THE CONTRACTOR OF THE TENANT SPACE TO START |
| WORK BEFORE THE CERTIFICATE OF COMPLETION OF THE BASE |
| BUILDING HAS BEEN ACHIEVED. 106.1.2 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 4) SHEET A0.01 THE FIRST FLOOR INDICATES AN ASSEMBLY |
| OCCUPANCY WITH A 15 SQ FT PERSON, UNCONCENTRATED, |
| PLEASE PROVIDE A FLOOR PLAN WITH TABLE AND CHAIRS AS |
| WELL AS FOR COMMON PATH OF TRAVEL. SHEET A1.00 ALSO IS |
| MISSING A LAYOUT OF FURNATURE. TABLE 1004.1.2 & 1013.3. |
| |
| 5) SHEET A1.00 PLEASE PROVIDE THE TENANT SEPERATION |
| WALLS AND WALL RATINGS AS WELL AS THE COMMON AREAS, |
| ALSO NOTE THE MECHANICAL MEZZANINE LEVEL WILL NEED TO |
| SHOW WHERE THE TENANT SEPERATION WALL WILL BE LOCATED. |
| SECTION 708.1. FIRE PARTITIONS, & TABLE 715.3. THIS |
| SHEET DOES INDICATE THE WALL RATING OF THE TENANT WALL |
| THAT DIVIDES THE PHOTO SHOP FROM THE MUSEUM BUT THE |
| NORTH WALLS OF THE MUSEUM ARE NOT INDICATED ON THE |
| PLANS. |
| |
| 6) SHEET A0.01 IT APPEARS THAT THE CORRIDOR OR HALL |
| (1.07) IS AN EXIT ACCESS CORRIDOR SINCE THERE ARE EXIT |
| SIGNS LEADING IN THE DIRECTION OF A 2HR RATED EXIT |
| PASSAGEWAY THAT LEADS FROM THE STAIRWELL. NOTE THE |
| CORRIDOR THAT LEADS BACK INTO THE CITY HALL PORTION OF |
| THIS BUILDING IS NOT REQUIRED TO BE RATED, FIRE OR |
| SMOKE, PER TABLE 1016.1. FOR A BUSINESS OCCUPANCY. BUT |
| THE ASSEMBLY OCCUPANCY THAT IS NOW BEING DIRECTEDED |
| INTO THIS CORRIDOR WILL REQUIRE A 1 HR FIRE RATING PER |
| TABLE 1016.1. |
| |
| 7) SHEET A1.00 THE PHOTO SHOP ROOMS 1.12, 1.13 & 1.14 |
| ALL NEED TO MEET THE REQUIREMENTS OF 1014.2.1 EXCEPTION |
| (2). THE DOORS ARE TO BE NOT LESS THAN 1/3RD OF THE |
| MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. |
| |
| 8) SHEET A0.01, A1.00 OR A1.01 IDENTIFY THE DOOR |
| OPENING NOR THE DOOR SIZE.106.1.2 / 715.3 & 1008.1.1. |
| |
| 9) SHEET A1.01 INDICATES THE CORRIDOR WALLS OR TENANT |
| SEPERATION WALLS AS 1 HR RATED PARTITIONS BY OTHERS, |
| THE CITY HALL APPROVED SET OF PLANS SHEET A1-2.2 DATE |
| STAMPED MAY 8, 2008 IS THE LATEST REVISION OF THIS AREA |
| AND DOES NOT INDICATE THESE WALLS. PLEASE COORDINATE |
| PLANS WITH THE BASE BUILDING DESIGNER AS TO WHO WILL |
| TAKE RESPONSIBILITY FOR THE DESIGN OF THIS AREA. |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| 708.1 FIRE PARTITIONS, TENANT SEPERATION WALLS. |
| |
| 10) SHEET A1.01 THE EXISTING WALL LINE LOCATED ALONG |
| SECTION LINE #5 ON THE BASE BUILDING SET OF PLANS WAS |
| CONSIDERED NON-RATED, NON SEPERATED USE. NOW WITH A NEW |
| TENANT THIS WALL WILL BECOME A TENANT SEPERATION WALL |
| REQUIRING A 1 HOUR FIRE RATING, SEE SECTION 708.1. |
| |
| 11) SHEET A1.01 NOTE ON THE LEFT SIDE OF PLANS IT |
| APPEARS TO BE A DISCREPANCY WITH THE WALL LEGEND ON THE |
| RIGHT SIDE OF PAGE. THIS NOTE IS DIRECTED TO 1 HR FIRE |
| RATING ON ALL TENANT SEPERATION WALLS BUT IS DIRECTED |
| TO A INTERIOR WALL LOCATED WITHIN THE TENANT SPACE. |
| DISCREPANCY. |
| |
| 12) SHEET A1.01 WITHIN THE PHOTORAPHY STUDIO THE PLANS |
| INDICATE USE OF A SELF -SUPPORTING FOLDING PARTITION, |
| NO STRUCTURAL MODIFICATIONS REQUIRED, PLEASE PROVIDE |
| PRODUCT INFORMATION ON SUCH A SYSTEM, |
| IS THIS SYSTEM SUPPORTED HOW? ADDITIONAL INFORMATION |
| REQUIRED106.1.2 . |
| |
| 13) SHEET A1.01 ROOM# 2.21 THE PHOTOGRAPHY STUDIO |
| SQUARE FOOTAGE IS 1711 SQ FT. THIS AREA APPEARS TO BE |
| AN ASSEMBLY OCCUPANCY WHEN THE FOLDING PARTITION IS NOT |
| IN USE. CLASSROOMS WTIH 20SQ FT PER |
| OCCUPANT PUTS A LOAD OF 86 OCCUPANTS, WHERE AS IF THE |
| USEAGE OF THE ROOM IS MORE IN LINE WITH A VOCATIONAL |
| SHOP THE SQUARE FOOTAGE USED PER OCCUPANT OF 50 WOULD |
| CREATE AN OCCUPANT LOAD OF 35. |
| TABLE 1016.1 WOULD REQUIRE UNDER AN ASSEMBLY OCCUPANCY |
| WHEN THE OCCUPANT LOAD IS EQUAL TO OR GREATER THAN 50 |
| WOULD REQUIRE 1 HR RATED CORRIDORS.TABLE 1016.1 PLEASE |
| PROVIDE A CODE ANYLISIS FOR THE SECOND FLOOR AS THE |
| FIRST FLOOR. |
| |
| 14) SHEET A1.01 ROOM 2.21 THE LOUNGE INDICATES WHAT |
| APPEARS TO BE A KITCHEN TYPE SINK, THERE ARE NO |
| ELEVATIONS OF THIS CABINETRY, PLEASE VARIFY COMPLIANCE |
| WITH: |
| 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE |
| COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH |
| FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION |
| 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW |
| FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| ACCESSIBLE ROUTE AND |
| SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH |
| THE SINK. |
| |
| 15) SHEET A4.00 DETAIL GYPSUM SOFFITS, THE PLANS DO NOT |
| DECLAIR WHAT TYPE OF FASTENER, OR FREQUENCY OF ANCHOR |
| THE VARIOUS WIDTH SOFFITS TO THE STRUCTURAL DECK ABOVE? |
| 106.1.2/ 2506.2 STANDARDS, |
| TABLE 2506.2 & 1604.3.6 DEFLECTION LIMITATIONS. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |