Plan Review Notes
Plan Review Notes For Permit 08090142
Permit Number 08090142
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-24 14:53:42BUILDING PLAN REVIEW
 PERMIT: 08090142 (PLAN REVIEW)
 ADD: 401 CLEMATIS ST. SUITE # .
 CONT: (PLAN REVIEW) CONTACT: TED DAVIS
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.THE COVER SHEEET
 NEGLECTS THE 2007 SUPPLEMENTS TO THE 2004 FBC, PLEASE
 CORRECT. 106.1.2 ADDITIONAL INFORMATION REQUIRED,
 553.73FL S S .
  
 1D) THIS TENANT SPACE IS LEASEABLE SPACE AND WILL
 REQUIRE A SUITE ADDRESS, TO BE PROVIDED BY ADDRESS
 TECHNITION JAMES JUDGE, AND WILL NEED TO BE ON THE
 PERMIT APPLICATIONAS WELL AS PLANS.
  
 2) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING
 DESIGNER WILL NEED TO REVIEW THE SUBMITTED PLANS AND
 AFFIX THEIR SHOP DRAWING STAMP ON THE PLANS. THE PLANS
 SUBMITTED MAY EFFECT THEIR ENERGY CALCULATION
 ASSUMPTIONS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING
 CONTRACTOR SHALL PROVIDE A NOTIRIZED LETTER INDICATING
 ALLOWING THE CONTRACTOR OF THE TENANT SPACE TO START
 WORK BEFORE THE CERTIFICATE OF COMPLETION OF THE BASE
 BUILDING HAS BEEN ACHIEVED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) SHEET A0.01 THE FIRST FLOOR INDICATES AN ASSEMBLY
 OCCUPANCY WITH A 15 SQ FT PERSON, UNCONCENTRATED,
 PLEASE PROVIDE A FLOOR PLAN WITH TABLE AND CHAIRS AS
 WELL AS FOR COMMON PATH OF TRAVEL. SHEET A1.00 ALSO IS
 MISSING A LAYOUT OF FURNATURE. TABLE 1004.1.2 & 1013.3.
  
 5) SHEET A1.00 PLEASE PROVIDE THE TENANT SEPERATION
 WALLS AND WALL RATINGS AS WELL AS THE COMMON AREAS,
 ALSO NOTE THE MECHANICAL MEZZANINE LEVEL WILL NEED TO
 SHOW WHERE THE TENANT SEPERATION WALL WILL BE LOCATED.
 SECTION 708.1. FIRE PARTITIONS, & TABLE 715.3. THIS
 SHEET DOES INDICATE THE WALL RATING OF THE TENANT WALL
 THAT DIVIDES THE PHOTO SHOP FROM THE MUSEUM BUT THE
 NORTH WALLS OF THE MUSEUM ARE NOT INDICATED ON THE
 PLANS.
  
 6) SHEET A0.01 IT APPEARS THAT THE CORRIDOR OR HALL
 (1.07) IS AN EXIT ACCESS CORRIDOR SINCE THERE ARE EXIT
 SIGNS LEADING IN THE DIRECTION OF A 2HR RATED EXIT
 PASSAGEWAY THAT LEADS FROM THE STAIRWELL. NOTE THE
 CORRIDOR THAT LEADS BACK INTO THE CITY HALL PORTION OF
 THIS BUILDING IS NOT REQUIRED TO BE RATED, FIRE OR
 SMOKE, PER TABLE 1016.1. FOR A BUSINESS OCCUPANCY. BUT
 THE ASSEMBLY OCCUPANCY THAT IS NOW BEING DIRECTEDED
 INTO THIS CORRIDOR WILL REQUIRE A 1 HR FIRE RATING PER
 TABLE 1016.1.
  
 7) SHEET A1.00 THE PHOTO SHOP ROOMS 1.12, 1.13 & 1.14
 ALL NEED TO MEET THE REQUIREMENTS OF 1014.2.1 EXCEPTION
 (2). THE DOORS ARE TO BE NOT LESS THAN 1/3RD OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED.
  
 8) SHEET A0.01, A1.00 OR A1.01 IDENTIFY THE DOOR
 OPENING NOR THE DOOR SIZE.106.1.2 / 715.3 & 1008.1.1.
  
 9) SHEET A1.01 INDICATES THE CORRIDOR WALLS OR TENANT
 SEPERATION WALLS AS 1 HR RATED PARTITIONS BY OTHERS,
 THE CITY HALL APPROVED SET OF PLANS SHEET A1-2.2 DATE
 STAMPED MAY 8, 2008 IS THE LATEST REVISION OF THIS AREA
 AND DOES NOT INDICATE THESE WALLS. PLEASE COORDINATE
 PLANS WITH THE BASE BUILDING DESIGNER AS TO WHO WILL
 TAKE RESPONSIBILITY FOR THE DESIGN OF THIS AREA.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
 708.1 FIRE PARTITIONS, TENANT SEPERATION WALLS.
  
 10) SHEET A1.01 THE EXISTING WALL LINE LOCATED ALONG
 SECTION LINE #5 ON THE BASE BUILDING SET OF PLANS WAS
 CONSIDERED NON-RATED, NON SEPERATED USE. NOW WITH A NEW
 TENANT THIS WALL WILL BECOME A TENANT SEPERATION WALL
 REQUIRING A 1 HOUR FIRE RATING, SEE SECTION 708.1.
  
 11) SHEET A1.01 NOTE ON THE LEFT SIDE OF PLANS IT
 APPEARS TO BE A DISCREPANCY WITH THE WALL LEGEND ON THE
 RIGHT SIDE OF PAGE. THIS NOTE IS DIRECTED TO 1 HR FIRE
 RATING ON ALL TENANT SEPERATION WALLS BUT IS DIRECTED
 TO A INTERIOR WALL LOCATED WITHIN THE TENANT SPACE.
 DISCREPANCY.
  
 12) SHEET A1.01 WITHIN THE PHOTORAPHY STUDIO THE PLANS
 INDICATE USE OF A SELF -SUPPORTING FOLDING PARTITION,
 NO STRUCTURAL MODIFICATIONS REQUIRED, PLEASE PROVIDE
 PRODUCT INFORMATION ON SUCH A SYSTEM,
 IS THIS SYSTEM SUPPORTED HOW? ADDITIONAL INFORMATION
 REQUIRED106.1.2 .
  
 13) SHEET A1.01 ROOM# 2.21 THE PHOTOGRAPHY STUDIO
 SQUARE FOOTAGE IS 1711 SQ FT. THIS AREA APPEARS TO BE
 AN ASSEMBLY OCCUPANCY WHEN THE FOLDING PARTITION IS NOT
 IN USE. CLASSROOMS WTIH 20SQ FT PER
 OCCUPANT PUTS A LOAD OF 86 OCCUPANTS, WHERE AS IF THE
 USEAGE OF THE ROOM IS MORE IN LINE WITH A VOCATIONAL
 SHOP THE SQUARE FOOTAGE USED PER OCCUPANT OF 50 WOULD
 CREATE AN OCCUPANT LOAD OF 35.
 TABLE 1016.1 WOULD REQUIRE UNDER AN ASSEMBLY OCCUPANCY
 WHEN THE OCCUPANT LOAD IS EQUAL TO OR GREATER THAN 50
 WOULD REQUIRE 1 HR RATED CORRIDORS.TABLE 1016.1 PLEASE
 PROVIDE A CODE ANYLISIS FOR THE SECOND FLOOR AS THE
 FIRST FLOOR.
  
 14) SHEET A1.01 ROOM 2.21 THE LOUNGE INDICATES WHAT
 APPEARS TO BE A KITCHEN TYPE SINK, THERE ARE NO
 ELEVATIONS OF THIS CABINETRY, PLEASE VARIFY COMPLIANCE
 WITH:
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE SINK.
  
 15) SHEET A4.00 DETAIL GYPSUM SOFFITS, THE PLANS DO NOT
 DECLAIR WHAT TYPE OF FASTENER, OR FREQUENCY OF ANCHOR
 THE VARIOUS WIDTH SOFFITS TO THE STRUCTURAL DECK ABOVE?
 106.1.2/ 2506.2 STANDARDS,
 TABLE 2506.2 & 1604.3.6 DEFLECTION LIMITATIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved