Plan Review Notes For Permit 08090106 |
Permit Number |
08090106 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-01-15 15:53:57 | ** DENIED REVIEW OF REVISIONS** | | | | | | 1) NOTE: THERE ARE A FEW ITEMS REDLINE DON PREVIOUS | | PLANS WHICH STILL NEED TO BE COORDINATED. | | THE PLANS STILL SHOW A TRANSFORMER IN FRONT OF THE | | PANELS. PLEASE VERIFY WHETHER OR NOT THE TRANSFORMER IS | | ABOVE PANELS GIVEN THE CLEARANCES PER 110.26 | | PLEASE COORDINATE RISER AS BOTH PANELS ARE SHOWN AS | | 125AMP MCB AND MLO ON EACH OF THE SCHEDULES YET THE | | RISER SHOWS BOTH OF THESE AS 225AMP MCB AND MLO. | | NEED TO VERIFY 240.21,310.16,240.4 | | THE NEW RECEPTACLES NEED TO BE SPECIFIC. THESE ARE | | NOTED ONLY AS RECEPTACLES. ALSO THE NEW 2-POLE | | RECEPTACLES NEED TO NOTED FOR WHAT THEY WILL SERVE. | | 408.4 | | | | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION, | | CLARITY AND COORDINATION. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | | | *** NOTED: THERE IS NO NEW LIGHTING PERMITTED EXCEPT IN | | ELEVATOR LOBBY AREA. |
|