Notes |
Date |
Text |
2008-10-01 15:27:02 | ***DENIED*** | | | | 1) MORE EXIT SIGNS AND EMERGENCY LIGHTING NEEDED IN | | OPEN WORK AREA 107. | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY | | WITH NFPA 241. | | | | 3) DOOR SCHEDULE REFERENCES THE INCORRECT CODE EDITION. | | LOCKING ARRANGEMENTS SHALL COMPLY WITH 101, SEC. | | 7.2.1.5. | | | | 4) RATED DOORS SHALL BE PROVIDED WITH UL LISTED | | CLOSERS. | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|