2008-09-12 12:04:50 | ** DENIED REVIEW ** |
| |
| |
| |
| |
| 1) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT IN CLOSET |
| AREA DOES NOT MEET 110.26,408.17, 240.24. THIS IS SHOWN |
| AS EXISTING HOWEVER BASED ON THIS BEING A LIFE SAFETY |
| AND FIRE HAZARD, EQUIPMENT AND SPACE LOCATION/LAYOUT |
| NEEDS TO CHANGE. |
| |
| 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.2.1, 2.2. |
| |
| |
| 3) NOTE: LIGHTING CONTROLS FOR NEW BEING INSTALLED NEED |
| TO MEET 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| |
| 4) NOTE: PANEL SCHEDULE FOR NEW CIRCUITS NEED TO BE |
| SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| |
| 5) NOTE: PLEASE PLACE NOTE ON PLANS FOR SERVER ROOM |
| THAT WIRING METHODS IN NEC 645 ARE NOT PERMITTED. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |