Plan Review Notes
Plan Review Notes For Permit 08090106
Permit Number 08090106
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-12 12:04:50** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT IN CLOSET
 AREA DOES NOT MEET 110.26,408.17, 240.24. THIS IS SHOWN
 AS EXISTING HOWEVER BASED ON THIS BEING A LIFE SAFETY
 AND FIRE HAZARD, EQUIPMENT AND SPACE LOCATION/LAYOUT
 NEEDS TO CHANGE.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.2.1, 2.2.
  
  
 3) NOTE: LIGHTING CONTROLS FOR NEW BEING INSTALLED NEED
 TO MEET 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: PANEL SCHEDULE FOR NEW CIRCUITS NEED TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
  
 5) NOTE: PLEASE PLACE NOTE ON PLANS FOR SERVER ROOM
 THAT WIRING METHODS IN NEC 645 ARE NOT PERMITTED.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  