Plan Review Notes For Permit 08090029 |
Permit Number |
08090029 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-09-05 10:38:10 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 225.30 NUMBER OF SUPPLIES | | WHERE MORE THAN ONE BUILDING OR OTHER STRUCTURE IS ON | | THE SAME PROPERTY AND UNDER SINGLE MANAGEMENT, EACH | | ADDITIONAL BUILDING OR OTHER STRUCTURE THAT IS SERVED | | BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF THE | | SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY | | ONE FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN | | 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION, | | A MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE | | CIRCUIT.*** THIS ARTICLE REQUIRES A DISCONNECTING MEANS | | AT THE PAVILION. SEE 225.31 AND 225.32 FOR LOCATION, | | 250.32 FOR GROUNDING REQUIREMENTS. LOCATE THIS | | EQUIPMENT ON THE PLAN, SHOW FEEDER INFORMATION ON A | | DIAGRAM PER 215.5. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|