Plan Review Notes
Plan Review Notes For Permit 08090029
Permit Number 08090029
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-05 10:38:10 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 225.30 NUMBER OF SUPPLIES
 WHERE MORE THAN ONE BUILDING OR OTHER STRUCTURE IS ON
 THE SAME PROPERTY AND UNDER SINGLE MANAGEMENT, EACH
 ADDITIONAL BUILDING OR OTHER STRUCTURE THAT IS SERVED
 BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF THE
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN
 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION,
 A MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE
 CIRCUIT.*** THIS ARTICLE REQUIRES A DISCONNECTING MEANS
 AT THE PAVILION. SEE 225.31 AND 225.32 FOR LOCATION,
 250.32 FOR GROUNDING REQUIREMENTS. LOCATE THIS
 EQUIPMENT ON THE PLAN, SHOW FEEDER INFORMATION ON A
 DIAGRAM PER 215.5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  