Plan Review Notes
Plan Review Notes For Permit 08090026
Permit Number 08090026
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-17 17:04:29 
 ** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE THE INCORRECT NFPA-70 IS STATED ON
 PLANS. IN FACT PLANS STATE A 2004 EDITION WHICH HAS
 NEVER EXISTED. PLEASE BE SURE THE FOLLOWING IS STATED
 ON ELECTRICAL PLANS AND COORDINATION ON ARCHITECTURAL
 IS DONE AT A MINIMUM.
 2002 NFPA-72
 2005 NPFA-70
 2003 NFPA-101
 2004 FBC W/ 2007 REVISIONS.
  
 FS 553.73
 FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION.
  
 ** SOME OF THESE ARE ALREADY NOTED AND CORRECT ONE
 ELECTRICAL PLANS, HOWEVER PLEASE COORDINATE BETWEEN
 ELECTRICAL AND ARCHITECTURAL PLANS.
  
 2) NOTE: PLEASE INCLUDE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.ABC.1.1,.1.2.
 ** PLEASE KNOW ANY NEW FIXTURES BEING INSTALLED SHALL
 MEET PRESCRIPTIVE REQUIREMENTS. IF NO NEW FIXTURES WILL
 BE INSTALLED AT ALL, THEN PLEASE PLACE NOTES ON PLANS
 WHICH STATE NO NEW FIXTURES PERMITTED. PLANS DO CONTAIN
 SOME NOTES ABOUT RELOCATING FIXTURES HOWEVER NEED TO BE
 EXPANDED AS THIS OFFICE HAS SEEN MANY PROJECTS WHICH
 FIXTURES ARE REPLACED WITH NEW AND THE LIGHTING
 ALLOWANCES ARE OVER THE ENERGY EFFICIENCY CODE.
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 COORDINATE WITH PANEL SCHEDULES.
 ** PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF EXIT
 AND EMERGENCY FIXTURES. SOME AREAS AS SHOWN WITHOUT
 CIRCUITING DO NOT MEET THE EXCEPTIONS IN SECTION AS
 NOTED.
  
 4) NOTE: PLEASE SEE 11-4.28.1,.2,.3 OF THE FBC. PLEASE
 INDICATE DEVICES, LOCATIONS, HEIGHTS, LEVELS ETC FOR
 MINIMUM COMPLIANCE FOR ADA.
  
 5) NOTE: IS THE SERVER ROOM AN IT ROOM PER NEC 645.2,
 NFPA-75? IF THIS ROOM IS NOT AN IT ROOM PLEASE PLACE
 NOTE ON PLANS WHICH STATES **** NO WIRING METHODS IN
 NEC 645 IS PERMITTED **** OR WORDS TO THAT AFFECT.
  
 6) NOTE: PLEASE SEE 250.20,250.50,250.66,250.30 AS NO
 GROUNDING ELECTRODE SYSTEM, CONDUCTORS ETC ARE SHOWN ON
 RISER FOR NEW TRANSFORMER.
  
 7) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT
 PROTECTION AS SHOWN FOR THE 50KVA TRANSFORMER IS TOO
 HIGH. (MAX 125%.) PLEASE ADJUST.
  
 8) NOTE: PLEASE SEE THE TAPS ON THE SECONDARY SIDE OF
 THE TRANSFORMER ARE TOO FAR AND DO NOT MEET 240.21.
 PLEASE ADJUST BY INCLUDING A MAIN ON THE SECONDARY SIDE
 OF THE TRANSFORMER WITHIN 10FT (CONDUCTOR LENGTHS).
  
 9) NOTE: PLEASE INCLUDE LOADS ON SERVICE. NOTES ON
 RISER MENTIONS ** IT IS IMPOSSIBLE* HOWEVER THE CODE
 CLEARLY PROVIDES METHODS TO DETERMINE EXISTING LOADS.
 PLEASE SEE 220.87
  
 10) NOTE: PLEASE BE SURE TO LIST AND IDENTIFY THE BACK
 UP POWER SOURCE AS *OPTIONAL STAND-BY ONLY* THIS IS NOT
 AN EMERGENCY/LIFE SAFETY OR LEGALLY REQUIRED SYSTEM.
  
 11) NOTE: WHERE ARE THE BATTERY BACK UP EGRESS LIGHTING
 REQUIRED PER NFPA-101 7.8.1.3, 7.9.2.1
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH WILL CHANGE
 AND/OR MAY NOT BE ON PLANS AT THIS TIME THERE MAY BE
 COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT
 THIS TIME.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  