Plan Review Notes
Plan Review Notes For Permit 08090019
Permit Number 08090019
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-03 09:30:502004 FBC W/2007 REVISIONS
 RE-ROOF
  
 DENIED BY BUILDING
 NOTE: THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C.
  
 1) SUBMIT 2 COPIES OF RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AT PERIMETER AND CORNER AREAS OF THE FLAT
 ROOF. SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT
 APPROVAL NOA FOR THE TAMKO MODIFIED ROOF SYSTEM.
  
 2) THE PHOTOGRAPHS FROM THE MY SAFE FLORIDA HOME
 INSPECTION REPORT DO NOT PROVIDE ADEQUATE PROOF THAT
 THE EXISTING ROOF TO WALL CONNECTIONS COMPLY WITH THE
 PRESCRIPTIVE REQUIREMENTS OF SECTION 201.3 OF THE
 HURRICANE MITIGATION RETROFIT REQUIREMENTS OF DCA RULE
 9B-3.0475. SUBMIT ADEQUATE PROOF THAT THE EXISTING
 STRAPS MEET THE PRESCRIPTIVE REQUIREMENTS. THE ONLY
 ALTERNATIVE IS AN EVALUATION REPORT FROM A FLORIDA
 LICENSED ENGINEER INDICATING THAT THE EXISTING STRAPS
 AND FASTENERS HAVE AN UPLIFT CAPACITY OF 500 LBS. OR
 HOW THIS WILL BE ACCOMPLISHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW