2008-09-10 14:14:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLAN SHOWS WHAT LOOKS LIKE AN A/C GRILL, IF SO SHOW
 THE GRILL SIZE, SUPPLY AIR CFM'S, AND DUCT (FLEX) SIZE
 ALSO STATE ON PLAN THAT THE DUCT IS GOING TO AN
 EXISTING A/C SYSTEM. PER 2004 WPB AMEND. 106.3.5.4
 (10).
  
 2) PROVIDE FOR RETURN AIR, PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729