Date |
Text |
2008-09-03 09:58:36 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE SCOPE OF WORK ON THE PERMIT APPLICATION STATES |
| "REPLACE OLD CAST IRON PIPE WITH PVC", HOWEVER THE |
| SUBMITTED PLANS ARE ONLY INDICATING THE ABOVE GROUND |
| SANITARY WASTE AND VENT PIPING BEING REPLACED. IS THE |
| UNDERGROUND SANITARY BEING REPLACED AS WELL? IF SO AN |
| ISOMETRIC WITH SIZING IS REQUIRED. PLEASE KNOW THAT THE |
| PERMIT APPLICATION STATES "DESCRIE PROJECT IN DETAIL |
| (FAILURE TO DO SO MAY RESULT IN DELAYS)" CLEARLY |
| INDICATE THE SCOPE OF WORK ON THE PERMIT APPLICATION AS |
| TO WHAT PIPING IS BEING REPLACED. PER (W.P.B. AS |
| AMENDED) SECTION 105 PERMITS. |
| |
| 2. THE KITCHEN SINK CAN NOT DRAIN INTO THE WET VENTED |
| 1/2 BATH. IT MUST DRAIN DOWNSTREAM OF THE 1/2 BATH. PER |
| FBC-2004 PLUMBING SECTION 909.1 WET VENT PERMITTED. |
| |
| 3. WATER-SEAL TRAPS ARE REQUIRED FOR THE FOLLOWING |
| FIXTURES. CLEARLY INDICATE THEM ON THE RESUBMITTAL. PER |
| FBC-2004 PLUMBING SECTION 1002.1 FIXTURE TRAPS. |
| |
| A} FIRST FLOOR KITCHEN SINK AND LAVATORY. |
| |
| B} SECOND FLOOR LAVATORY. |
| |
| 4. A CLEANOUT IS REQUIRED AT THE BASE OF THE SECOND |
| FLOOR SOIL STACK. PER FBC-2004 PLUMBING SECTION 708.3.5 |
| BASE OF STACK. |
| |
| 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| (W.P.B. AS AMENDED) SECTION *106.3.4.3. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |