Date |
Text |
2008-09-17 14:12:52 | 2004 FBC W/2007 REVISIONS |
| R-3 ADDITION |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. FS 713 |
| |
| 2) THE EXPOSURE CATEGORY FOR THE STRUCTURE IS |
| INCORRECTLY SPECIFIED AS CATEGORY B ON SHEETS A1 AND |
| A4. SEE R301.2.1.4 EXPOSURE CATEGORY. 3. EXPOSURE C. |
| OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING |
| SURFACE UNDULATIONS OR OTHER IRREGULARITIES, HAVING |
| HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING |
| MORE THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE |
| IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY |
| BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE |
| THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF |
| EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE |
| OF MORE THAN 600 FEET (182.9 M). PLEASE CORRECT AND |
| REVISE COMPONENT AND CLADDING PRESSURES ON A4. |
| |
| 3) THE MINIMUM WALL INSULATION IS SPECIFIED AS R-4.1 ON |
| THE WALL SECTION ON SHEET A4. THE ENERGY CALCULATION |
| FORM LISTS A MINIMUM OF R-5. IF YOU USE THE |
| PRESCRIPTIVE METHOD C OF THE ENERGY CODE, THE MINIMUM |
| INSULATION FOR MASONRY WALLS IS R-5. PLEASE CORRECT. |
| FBC 13-600. |
| |
| 4) THE WINDOW BUCK DETAILS ON A4 SHOW THE DRYWALL |
| SUPPORTING A PORTION OF THE WINDOW FRAMES. PLEASE |
| REVISE. SEE R613.6.1.1 MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBSTRATE. UNLESS OTHERWISE TESTED, BUCKS |
| SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR |
| DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS |
| PROVIDED. |
| |
| 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR 8" WIDE |
| LINTELS. THE NOA THAT WAS SUBMITTED IS FOR 4", 6" AND |
| 12" LINTELS. FAC RULE 9B-72. |
| |
| 6) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF |
| COVERING. FAC RULE 9B-72. |
| |
| 7) THE VALUATION OF THE WORK HAS BEEN INCREASED TO |
| $40,509.00, ADDITIONAL PERMIT FEES OF $174.02 ARE DUE. |
| |