Plan Review Notes For Permit 08080543 |
Permit Number |
08080543 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-26 16:54:50 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | | 2} PROVIDE LOAD CALCULATIONS PER ARTICLE 220, THE | | CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED | | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS | | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND | | FACTORS, ARTICLE 215.5 NEC 2005.*** THIS COMMENT WAS | | GENERATED DUE TO CHANGING THE LOAD TO SINGLE PHASE. | | | | 3} INCLUDE THE CONDUCTOR SIZE OF THE FEEDERS TO THE NEW | | PANEL.215.5 | | | | 4} IF REPLACING THE FEEDER CONDUIT INDICATE TYPE (PVC, | | GRC, ETC) SUBMIT AN ELEVATION SHOWING ROUTING AND | | INDICATE THE TYPE OF FIRESTOPPING SYSTEM BEING USED. | | 711.2 FBC. | | | | 5} PROVIDE A FLOOR PLAN INDICATING THE LOCATION OF THE | | PANEL BEING REPLACED. 106.3.5.1.2 FBC AS AMENDED. | | | | 6} INDICATE THE LOCATION OF THE DICONNECTING MEANS FOR | | THE SERVICE/FEEDER.215.5 NEC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|