 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
  
 2} PROVIDE LOAD CALCULATIONS PER ARTICLE 220, THE
 CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS, ARTICLE 215.5 NEC 2005.*** THIS COMMENT WAS
 GENERATED DUE TO CHANGING THE LOAD TO SINGLE PHASE.
  
 3} INCLUDE THE CONDUCTOR SIZE OF THE FEEDERS TO THE NEW
 PANEL.215.5
  
 4} IF REPLACING THE FEEDER CONDUIT INDICATE TYPE (PVC,
 GRC, ETC) SUBMIT AN ELEVATION SHOWING ROUTING AND
 INDICATE THE TYPE OF FIRESTOPPING SYSTEM BEING USED.
 711.2 FBC.
  
 5} PROVIDE A FLOOR PLAN INDICATING THE LOCATION OF THE
 PANEL BEING REPLACED. 106.3.5.1.2 FBC AS AMENDED.
  
 6} INDICATE THE LOCATION OF THE DICONNECTING MEANS FOR
 THE SERVICE/FEEDER.215.5 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  