2008-09-08 10:19:18 | |
| 9-8-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 3) 61G1-16.004 TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| |
| 4) THE ADDRESS OF THE PROJECT SHALL BE INDICATED ON |
| EACH SHEET INCLUDING THE SUITE NUMBER. THIS INFORMATION |
| IS TO PROVIDE CONFORMITY TO THE DEPARTMENT RECORD |
| RETENTION PROGRAM. FBC 106.1.3* |
| |
| 5) THE APPLICATION INDICATES THE PROJECT AS AN INTERIOR |
| REMODEL. ARE THERE ANY WALLS, DOORS OR ANY OTHER |
| SYSTEMS BEING ADDED OR DEMOED? CONSTRUCTION DOCUMENTS |
| SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC |
| 106.1.1. |
| |
| 6) IF THIS IS TRULY AN INTERIOR REMODEL, STATE THE |
| LEVEL OF ALTERATION ON THE PLANS PER FBC (EXISTING) |
| 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |
| |
| |
| |