2008-09-26 10:21:13 | DENIED |
| REFERENCE: FBC-2004 CHAPTER 1 |
| FBC-2004 BUILDING |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. SHT A.1 SHOW THE CLEAR FLOOR SPACE REQUIRED FOR ALL |
| ACCESSIBLE FIXTURES ON THE FLOOR PLAN. SECTIONS |
| 11-4.15.5, 11-4.16.2, 11-4.19.3 & 11-4.24.5. (CABINET |
| DOORS ARE NOT APPROVED AT THE BREAK SINK). |
| ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| SHOWN ON SHT A.1 FOR THE BREAK ROOM SINK, 11-4.24.5. |
| |
| 2. SHT A.1 THE TURNING AREA SHALL BE UNOBSTRUCTED. |
| TOILET ROOMS 109 & 112 SHOW THE WATER CLOSET IN THE |
| TURNING AREA. SECTION 11-4.22.3. |
| ****RESPONSE NOTED, BUT THE TURNING AREA SHALL BE SHOWN |
| IN TOILET ROOM 109 AND THE W/C SHALL BE SHOWN AT 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO SHOW |
| THE TOILET ROOM CAN BE ADAPTABLE WITHOUT STRUCTURAL |
| CHANGES. SECTION 11-4.1.3(11) & DEFINITIONS SECTION |
| 11-3.5. |
| |
| 3. OK |
| 4. OK |
| 5. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |