2008-08-26 11:36:01 | DENIED |
| REFERENCE: FBC-2004 CHAPTER 1 |
| FBC-2004 BUILDING |
| |
| 1. SHT A.1 SHOW THE CLEAR FLOOR SPACE REQUIRED FOR ALL |
| ACCESSIBLE FIXTURES ON THE FLOOR PLAN. SECTIONS |
| 11-4.15.5, 11-4.16.2, 11-4.19.3 & 11-4.24.5. (CABINET |
| DOORS ARE NOT APPROVED AT THE BREAK SINK). |
| |
| 2. SHT A.1 THE TURNING AREA SHALL BE UNOBSTRUCTED. |
| TOILET ROOMS 109 & 112 SHOW THE WATER CLOSET IN THE |
| TURNING AREA. SECTION 11-4.22.3. |
| |
| 3. SHT A.3 FINISH SCHEDULE FOR ROOMS 109, 112, 120 & |
| 134. SECTION 1210.2 REQUIRES WALLS WITHIN 2 FEET OF A |
| WATER CLOSET TO HAVE A SMOOTH, HARD, NONABSORBENT |
| SURFACE UP TO 4 FEET ABOVE FINISHED FLOOR. EPOXY PAINT |
| DOES NOT MEET THE HARD REQUIREMENT. PLEASE INDICATE HOW |
| THE REQUIREMENT FOR A HARD SURFACE WILL BE COMPLIED |
| WITH. |
| |
| 4. SHT A.3 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING: |
| |
| ___FOR DRINKING FOUNTAINS: |
| A. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. |
| |
| ___FOR WATER CLOSETS: |
| A. 11-4.16.5 FLUSH CONTROLS. |
| |
| ___FOR LAVS: |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| B. 11-4.19.5 FAUCETS |
| |
| 5. SHT A.5 DETAIL 11/A.5 SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| |
| ___FOR BREAK ROOM SINK: |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.6 EXPOSED PIPES & SURFACES |
| C. 11-4.24.7 FAUCETS |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |