Plan Review Notes
Plan Review Notes For Permit 08080467
Permit Number 08080467
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-29 13:43:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGES AC-1 AND AC-2 SHOW DUCT SMOKE DETECTORS AT ALL
 AIR HANDLING UNITS, BUT CONTROL SEQUENCE NOTE #3 CALLS
 FOR DUCT DETECTORS ON ONLY 3 UNITS. ALSO, PAGE E.1
 SHOWS DUCT DETECTORS ON ALL UNITS (IT IS ASSUMED THAT
 THE ELECTRICAL PLAN SHOWS DUCT DETECTORS AT ALL UNITS,
 SINCE THE SYMBOL ?SD? IS NOT SHOWN ON THE ELECTRICAL
 SYMBOL LEGEND). PLEASE COORDINATE PLANS AND NOTES TO
 SHOW THE INTENDED SCOPE OF WORK IN ACCORDANCE WITH FBCB
 106.1.1 AND FBCM 606.2.
  
 2. PAGE AC-2 FAN AND ROOF VENT SCHEDULE SHOWS NOTE 3
 APPLYING TO ALL EXHAUST FANS. THIS NOTE CALLS FOR A 12?
 HIGH ROOF CURB. THE FLOOR PLAN ON AC-1 NOTE SHOWS
 CEILING MOUNTED EXHAUST FANS WITH GOOSENECK VENTS ON
 THE ROOF. WHAT IS THE PURPOSE OF THE 12? HIGH CURBS ON
 THE SCHEDULE? PLEASE COORDINATE PLANS AND NOTES SHOWING
 COMPLIANCE WITH FBCM 501.2, FBCB 106.1.1 AND FBCB 1509
  
 3. BY WHAT MEANS ARE THE TOILET ROOM EXHAUST FANS BEING
 CONTROLLED? THERE IS NO INDICATION ON MECHANICAL PLANS
 AND THE FANS DO NOT APPEAR AT ALL ON THE ELECTRICAL
 FLOOR PLANS AT ALL. PLEASE CLARIFY. SHOW COMPLIANCE
 WITH ASHRAE 62.1 SECTION 5.4.
  