Plan Review Notes For Permit 08080467 |
Permit Number |
08080467 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-29 13:43:53 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PAGES AC-1 AND AC-2 SHOW DUCT SMOKE DETECTORS AT ALL | | AIR HANDLING UNITS, BUT CONTROL SEQUENCE NOTE #3 CALLS | | FOR DUCT DETECTORS ON ONLY 3 UNITS. ALSO, PAGE E.1 | | SHOWS DUCT DETECTORS ON ALL UNITS (IT IS ASSUMED THAT | | THE ELECTRICAL PLAN SHOWS DUCT DETECTORS AT ALL UNITS, | | SINCE THE SYMBOL ?SD? IS NOT SHOWN ON THE ELECTRICAL | | SYMBOL LEGEND). PLEASE COORDINATE PLANS AND NOTES TO | | SHOW THE INTENDED SCOPE OF WORK IN ACCORDANCE WITH FBCB | | 106.1.1 AND FBCM 606.2. | | | | 2. PAGE AC-2 FAN AND ROOF VENT SCHEDULE SHOWS NOTE 3 | | APPLYING TO ALL EXHAUST FANS. THIS NOTE CALLS FOR A 12? | | HIGH ROOF CURB. THE FLOOR PLAN ON AC-1 NOTE SHOWS | | CEILING MOUNTED EXHAUST FANS WITH GOOSENECK VENTS ON | | THE ROOF. WHAT IS THE PURPOSE OF THE 12? HIGH CURBS ON | | THE SCHEDULE? PLEASE COORDINATE PLANS AND NOTES SHOWING | | COMPLIANCE WITH FBCM 501.2, FBCB 106.1.1 AND FBCB 1509 | | | | 3. BY WHAT MEANS ARE THE TOILET ROOM EXHAUST FANS BEING | | CONTROLLED? THERE IS NO INDICATION ON MECHANICAL PLANS | | AND THE FANS DO NOT APPEAR AT ALL ON THE ELECTRICAL | | FLOOR PLANS AT ALL. PLEASE CLARIFY. SHOW COMPLIANCE | | WITH ASHRAE 62.1 SECTION 5.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | 2008-08-28 16:11:50 | | | |
|