Plan Review Notes
Plan Review Notes For Permit 08080467
Permit Number 08080467
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-11 10:12:50***DENIED***
  
 1) ILLUSTRATE FIRE SPRINKLER LAYOUT ON PLANS.
 ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT WILL BE
 REQUIRED PRIOR TO INSTALLATION.
  
 2) WILL A FIRE ALARM SYSTEM BE PROVIDED. IF SO,
 ILLUSTRATE APPLICABLE EQUIPMENT SHOWING MINIMUM LEVELS
 AND ADA REQUIREMENTS.
  
 3) IN ADDITION TO FAN SHUT DOWN, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW