2008-09-03 14:16:07 | |
| |
| |
| |
| |
| ** DENIED ** |
| |
| |
| |
| 1) NOTE: PLEASE BE SURE TO COORDINATE ALL SYMBOLS ON |
| PLANS WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE |
| THE COMMENTS FROM THE MECHANICAL REVIEW WITH RESPECT TO |
| THE SMOKE DETECTORS FOR AC SYSTEM/DUCTS. |
| FBC 106.1.1 FOR CLARITY AND COORDINATION |
| |
| 2) NOTE: PLEASE BE SURE THE PLANS STATE 517 PART TWO. |
| PLANS DO TALK ABOUT REDUNDANT GROUNDING HOWEVER THERE |
| ARE OTHER REQUIREMENTS FOR WIRING IN THIS OCCUPANCY. |
| |
| 3) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING |
| CODES; |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 ( WHERE APPLICABLE). |
| |
| PLANS MAY NOT STATE LATEST EDITION. |
| |
| 4) NOTE: THIS IS A SINGLE TENANT AS SHOWN, ONLY ONE |
| METER IS PERMITTED. |
| THIS ITEM IS NOT ADDRESSED IN THE NEC. THE RISER SHOWS |
| A NEW 600AMP SERVICE CAPACITY HOWEVER NO LOAD |
| CALCULATIONS WERE SUBMITTED FOR THE ENTIRE BUILDING. |
| 220, 230.70, 240.4, 310.16 |
| |
| 5) NOTE: PLEASE PROVIDE NOTES PER |
| 13-413.1.ABC.2.1,.2.2. |
| |
| 6) NOTE: PLEASE EXPLAIN HOW THE #6 AS SHOWN AS A |
| GROUNDING ELECTRODE CONDUCTOR MEETS 250.66, 250.50 |
| |
| 7) NOTE: PLEASE VERIFY IF BUILDING WILL HAVE A FIRE |
| ALARM SYSTEM. IF SO PLEASE SEE FBC 11-4.28.1,.2 AND .3 |
| FOR MINIMUM LEVELS AND LOCATIONS OF DEVICES TO MEET ADA |
| REQUIREMENTS. |
| |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |