Plan Review Notes
Plan Review Notes For Permit 08080467
Permit Number 08080467
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-03 14:16:07 
  
  
  
  
 ** DENIED **
  
  
  
 1) NOTE: PLEASE BE SURE TO COORDINATE ALL SYMBOLS ON
 PLANS WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE
 THE COMMENTS FROM THE MECHANICAL REVIEW WITH RESPECT TO
 THE SMOKE DETECTORS FOR AC SYSTEM/DUCTS.
 FBC 106.1.1 FOR CLARITY AND COORDINATION
  
 2) NOTE: PLEASE BE SURE THE PLANS STATE 517 PART TWO.
 PLANS DO TALK ABOUT REDUNDANT GROUNDING HOWEVER THERE
 ARE OTHER REQUIREMENTS FOR WIRING IN THIS OCCUPANCY.
  
 3) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING
 CODES;
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 ( WHERE APPLICABLE).
  
 PLANS MAY NOT STATE LATEST EDITION.
  
 4) NOTE: THIS IS A SINGLE TENANT AS SHOWN, ONLY ONE
 METER IS PERMITTED.
 THIS ITEM IS NOT ADDRESSED IN THE NEC. THE RISER SHOWS
 A NEW 600AMP SERVICE CAPACITY HOWEVER NO LOAD
 CALCULATIONS WERE SUBMITTED FOR THE ENTIRE BUILDING.
 220, 230.70, 240.4, 310.16
  
 5) NOTE: PLEASE PROVIDE NOTES PER
 13-413.1.ABC.2.1,.2.2.
  
 6) NOTE: PLEASE EXPLAIN HOW THE #6 AS SHOWN AS A
 GROUNDING ELECTRODE CONDUCTOR MEETS 250.66, 250.50
  
 7) NOTE: PLEASE VERIFY IF BUILDING WILL HAVE A FIRE
 ALARM SYSTEM. IF SO PLEASE SEE FBC 11-4.28.1,.2 AND .3
 FOR MINIMUM LEVELS AND LOCATIONS OF DEVICES TO MEET ADA
 REQUIREMENTS.
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  