Plan Review Notes
Plan Review Notes For Permit 08080452
Permit Number 08080452
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-05 12:53:08 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2}702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY SYSTEM
 SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE SUPPLY
 OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE TIME.
 THE LOAD CALCULATION SUBMITTED EXCEEDS THE GENERATOR
 OUTPUT IN THE GENERATOR SPECIFICATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  