2008-09-09 11:20:172004 FBC W/2007 REVISIONS
 RESIDENTIAL GENERATOR
  
 DENIED BY BUILDING
  
 1) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING. GENERATOR SLAB &
 ANCHOR REQUIREMENT PLEASE PROVIDE SIZE OF
 GENERATOR(WXL), PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF FASTENER, AND THE
 MINIMUM EDGE DISTANCE THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION. SPECIFY DIMENSIONS OF CONCETE SLAB,
 REINFORCEMENT, ETC.
  
 2) PLEASE PROVIDE 2 COPIES OF A SITE PLAN. PROVIDE
 PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES
 BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL
 TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1. WHERE LOCATED ADJACENT TO WALKWAYS, THE TERMINATION
 OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
 2. VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) ABOVE
 ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 MM).
 3. THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 INTO THE BUILDING.
 4. THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5. THE VENT TERMINATION SHALL NOT BE MOUNTED DIRECTLY
 ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY FROM AN
 OIL TANK
 VENT OR GAS METER.
 6. THE BOTTOM OF THE VENT TERMINATION SHALL BE LOCATED
 AT LEAST 12 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 1. WHERE LOCATED ADJACENT TO WALKWAYS, THE TERMINATION
 OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
 2. VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) ABOVE
 ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 MM).
 3. WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4. THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219 MM)
 BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 FOR THE BUILDING. 5. A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT SYSTEM.
 6. THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM LOT LINES
 OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO THE
 CENTERLINE OF THE
 STREET OR PUBLIC WAY. TING THE LOCATION OF THE
 GENERATOR IN RELATIONSHIP TO OTHER STRUCTURES, PLEASE
 NOTE IF THERE ARE STRUCTURES WITHIN 10'-0" OF THE
 GENERATOR OPENINGS SUCH AS WINDOWS AND DOORS.
 ADDITIONAL INFORMATION REQUIRED. POSSIBLE MECHANICAL
 ISSUES.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 4) SPECIFY WIND DESIGN DATA ON THE SLAB AND ANCHORING
 PLANS 1603.1.4 WIND DESIGN DATA. BASIC WIND SPEED
 (3-SECOND GUST), MILES PER HOUR (KM/HR).
  
 5) THE EQUIPMENT IS LOCATED IN AN A5 FLOOD ZONE AN
 ELEVATION OF 7' 6" TO THE TOP OF THE GENERATOR SLAB IS
 REQUIRED.
  