Notes
Date Text
2008-09-02 14:46:32REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED UNDER THE FOLLOWING CODES:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS SHALL BE ADDRESSED, CORRECTIONS
 MADE TO THE PLANS AND RESUBMITTED:
  
 MH-102: BASED ON THE LOCATION OF FIRE RATED WALLS SHOWN
 ON PAGE GV-102, THERE ARE AT LEAST 8 DUCT PENETRATIONS
 OF A 1-HOUR RATED WALL WHICH ARE NOT SHOWN ON PLANS TO
 BE PROTECTED AS REQUIRED IN ACCORDANCE WITH FBCM 607.5.
 SHOW TYPE AND LOCATION OF PROTECTION AT EACH DUCT
 PENETRATION OF A FIRE RATED ASSEMBLY IN ACCORDANCE WITH
 THIS SECTION AND FBCM 607.8.
 NOTE: ONE SET OF SUBMITTED PLANS IS MARKED-UP FOR
 REFERENCE TO SHOW THESE LOCATIONS.
  