Plan Review Notes For Permit 08080450 |
Permit Number |
08080450 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-09-12 12:05:40 | ***PROVISO*** | | | | 1) PLEASE ADD NFPA 13, 2003 TO CODE DATA ON SHEET GV | | 101. | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | 3) EXTERIOR DOORS SHOWN ON SHEET AF 201 ARE NOT | | IDENTIFIED. IF DOORS LEAD TO AN INTERIOR STAIRWELL OR | | SEPARATE SUITE, IDENTIFICATION OF SUCH SHALL BE | | REQUIRED. | | | | 4) PLEASE SEE MECHANICAL COMMENT REGARDING DUCT | | PENETRATIONS. | | | | PLANS WILL BE STAMPED WHEN RETURNED WITH THESE AND | | OTHER REVIEW CORRECTIONS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|